43502

Pre-Start Contact Config

Int32

n/a

n/a

RW

0 = Open After Disconnect

1 = Closed While Running

43504

System Units

Int32

n/a

n/a

RW

0 = English

1 = Metric

43506

Battery Volts

Int32

n/a

n/a

RW

0 = 12V

1 = 24V

43508

Off Mode Status

Int32

n/a

n/a

R

0 = Disable

1 = Enable

43510

Run Mode Status

Int32

n/a

n/a

R

0 = Disable

1 = Enable

43512

Auto Mode Status

Int32

n/a

n/a

R

0 = Disable
1 = Enable

43514

Virtual Input 1 Status

Int32

n/a

n/a

R

0 = Disable
1 = Enable

43516

Virtual Input 2 Status

Int32

n/a

n/a

R

0 = Disable
1 = Enable

43518

Virtual Input 3 Status

Int32

n/a

n/a

R

0 = Disable
1 = Enable

43520

Virtual Input 4 Status

Int32

n/a

n/a

R

0 = Disable
1 = Enable

43522

RTC Clock Hour

Int32

Hour

n/a

RW

0 - 23

43524

RTC Minute

Int32

Minute

n/a

RW

0 - 59

43526

RTC Second

Int32

Second

n/a

RW

0 - 59

43528

RTC Month

Int32

n/a

n/a

RW

1 - 12

43530

RTC Day

Int32

n/a

n/a

RW

1 - 31

43532

RTC Year

Int32

n/a

n/a

RW

0 - 99

43534

Reserved

43536

Gen PT Primary

Int32

Volt

n/a

RW

1 - 99999

43538

Gen PT Secondary

Int32

Volt

n/a

RW

1 - 480

43540

Gen CT Primary

Int32

Amp

n/a

RW

1 - 9999

43542

Bus PT Primary

Int32

Volt

n/a

RW

1 - 99999

43544

Bus PT Secondary

Int32

Volt

n/a

RW

1 - 480

43546

Cranking Style

Uint32

n/a

n/a

RW

0 = Continuous
1 = Cycle

43548

Number of Crank Cycles

Uint32

n/a

n/a

RW

1 - 7

43550

Cycle Crank Time

Unit32

Second

n/a

RW

5 - 15

43552

Continuous Crank Time

Unit32

Second

n/a

RW

5 - 60

43554

Crank Disconnect Limit

Uint32

Percent

n/a

RW

10 - 100

43556

Pre Crank Delay

Uint32

Second

n/a

RW

0 - 30

43558

Configured Gen Connection

Uint32

n/a

n/a

RW

0 = Delta
1 = Wye

2 = 1-phase AB
3 = 1-phase AC

4 = Grounded Delta

43560

Gen Rated Frequency

Int32

Hertz

n/a

RW

0 = 50 Hz

1 = 60 Hz

43562

Rated kW

Uint32

kilowatt

n/a

RW

5 - 9999

43564

Rated Engine RPM

Uint32

RPM

n/a

RW

750 - 3600

43566

No Load Cool Down Time

Uint32

Minute

n/a

RW

0 - 60

43568

EPS Current Threshold

Int32

Percent CT Pri

n/a

RW

3 - 10

43570

Fuel Level Function

Uint32

n/a

n/a

RW

0 = Disable
1 = Fuel Lvl

2 = Natural Gas
3 = Propane

43572

Number Flywheel Teeth

Uint32

n/a

n/a

RW

1 - 500

43574

Speed Signal Source

Uint32

n/a

n/a

RW

1 = MPU

2 = Gen Freq
3 = MPU Freq

43576

NFPA Level

Uint32

n/a

n/a

RW

0 = Zero
1 = One

2 = Two

43578

Horn Enable

Int32

n/a

n/a

RW

0 = Disabled

1 = Enabled

43580

Single-Phase Override Sensing

Uint32

n/a

n/a

RW

0 = AB

1 = AC

43582

Reserved

43584

LCD Contrast Value

Uint32

n/a

n/a

RW

0 - 100

43586

Front Panel Sleep Mode

Uint32

n/a

n/a

RW

0 = Disabled

1 = Enabled

43588

Reserved

43590

UTC Offset

Int32

Minute

n/a

RW

(-1440) - 1440

43592

DST Configuration

Int32

n/a

n/a

RW

0 = Disabled
1 = Floating

2 = Fixed

43594

Start/End Time Reference

Int32

n/a

n/a

RW

0 = Local Time

1 = UTC Time

43596

DST Bias Hours

Int32

n/a

n/a

RW

0 - 23

43598

DSP Bias Minutes

Int32

n/a

n/a

RW

0 - 59