Bus condition – Basler Electric DGC-2020HD Modbus Protocol User Manual
Page 62
![background image](https://www.manualsdir.com/files/773959/content/doc062.png)
56
9469300991 Rev A
Default Register Table
DGC-2020HD Modbus
™ Protocol
Name
Description
Group Register Type Bytes R/W
Unit
Range
Breaker Local Request
Generation
Mains Breaker Open Config
GG
2696
Uint32 4
R W n/a
Generator Start=0
Generator Stable=1
Breaker Local Request
Generation
Mains Zero Power Flow Level
GG
2698
Uint32 4
R W Percent
1 - 100
Breaker Local Request
Generation
Open Transition Delay
GG
2700
Uint32 4
R W Decisecond 0 - 100,000
Bus Condition
Name
Description
Group
Register
Type
Bytes
R/W
Unit
Range
Gen Condition
Dead Pickup
SG0 1P
3000
Float
4
R W
Volt
0 - 4800
Gen Condition
Dead Time Delay
SG0 1P
3002
Float
4
R W
Second
0.1 - 600
Gen Condition
Stable Undervoltage Pickup
SG0 1P
3004
Float
4
R W
Volt
10 - 99999
Gen Condition
Stable Undervoltage Dropout
SG0 1P
3006
Float
4
R W
Volt
10 - 99999
Gen Condition
Stable Overvoltage Pickup
SG0 1P
3008
Float
4
R W
Volt
10 - 99999
Gen Condition
Stable Overvoltage Dropout
SG0 1P
3010
Float
4
R W
Volt
10 - 99999
Gen Condition
Stable Underfrequency Pickup
SG0 1P
3012
Float
4
R W
Hertz
46 - 64
Gen Condition
Stable Underfrequency Dropout
SG0 1P
3014
Float
4
R W
Hertz
46 - 64
Gen Condition
Stable Overfrequency Pickup
SG0 1P
3016
Float
4
R W
Hertz
46 - 64
Gen Condition
Stable Overfrequency Dropout
SG0 1P
3018
Float
4
R W
Hertz
46 - 64
Gen Condition
Stable Time Delay
SG0 1P
3020
Float
4
R W
Second
0.1 - 600
Gen Condition
Fail Time Delay
SG0 1P
3022
Float
4
R W
Second
0.1 - 600
Gen Condition
Low-Line Scale
SG0 1P
3024
Float
4
R W
n/a
0.001 - 3
Gen Condition
Alternate Frequency Scale
SG0 1P
3026
Float
4
R W
n/a
0.001 - 100
Gen Condition
Dead Pickup
SG0 3P
3028
Float
4
R W
Volt
0 - 4800
Gen Condition
Dead Time Delay
SG0 3P
3030
Float
4
R W
Second
0.1 - 600
Gen Condition
Stable Undervoltage Pickup
SG0 3P
3032
Float
4
R W
Volt
10 - 99999
Gen Condition
Stable Undervoltage Dropout
SG0 3P
3034
Float
4
R W
Volt
10 - 99999
Gen Condition
Stable Overvoltage Pickup
SG0 3P
3036
Float
4
R W
Volt
10 - 99999
Gen Condition
Stable Overvoltage Dropout
SG0 3P
3038
Float
4
R W
Volt
10 - 99999
Gen Condition
Stable Underfrequency Pickup
SG0 3P
3040
Float
4
R W
Hertz
46 - 64
Gen Condition
Stable Underfrequency Dropout
SG0 3P
3042
Float
4
R W
Hertz
46 - 64
Gen Condition
Stable Overfrequency Pickup
SG0 3P
3044
Float
4
R W
Hertz
46 - 64
Gen Condition
Stable Overfrequency Dropout
SG0 3P
3046
Float
4
R W
Hertz
46 - 64
Gen Condition
Stable Time Delay
SG0 3P
3048
Float
4
R W
Second
0.1 - 600
Gen Condition
Fail Time Delay
SG0 3P
3050
Float
4
R W
Second
0.1 - 600
Gen Condition
Low-Line Scale
SG0 3P
3052
Float
4
R W
n/a
0.001 - 3
Gen Condition
Alternate Frequency Scale
SG0 3P
3054
Float
4
R W
n/a
0.001 - 100
Gen Condition
Dead Pickup
SG1 1P
3056
Float
4
R W
Volt
0 - 4800
Gen Condition
Dead Time Delay
SG1 1P
3058
Float
4
R W
Second
0.1 - 600
Gen Condition
Stable Undervoltage Pickup
SG1 1P
3060
Float
4
R W
Volt
10 - 99999
Gen Condition
Stable Undervoltage Dropout
SG1 1P
3062
Float
4
R W
Volt
10 - 99999
Gen Condition
Stable Overvoltage Pickup
SG1 1P
3064
Float
4
R W
Volt
10 - 99999
Gen Condition
Stable Overvoltage Dropout
SG1 1P
3066
Float
4
R W
Volt
10 - 99999
Gen Condition
Stable Underfrequency Pickup
SG1 1P
3068
Float
4
R W
Hertz
46 - 64
Gen Condition
Stable Underfrequency Dropout
SG1 1P
3070
Float
4
R W
Hertz
46 - 64
Gen Condition
Stable Overfrequency Pickup
SG1 1P
3072
Float
4
R W
Hertz
46 - 64
Gen Condition
Stable Overfrequency Dropout
SG1 1P
3074
Float
4
R W
Hertz
46 - 64
Gen Condition
Stable Time Delay
SG1 1P
3076
Float
4
R W
Second
0.1 - 600
Gen Condition
Fail Time Delay
SG1 1P
3078
Float
4
R W
Second
0.1 - 600
Gen Condition
Low-Line Scale
SG1 1P
3080
Float
4
R W
n/a
0.001 - 3
Gen Condition
Alternate Frequency Scale
SG1 1P
3082
Float
4
R W
n/a
0.001 - 100
Gen Condition
Dead Pickup
SG1 3P
3084
Float
4
R W
Volt
0 - 4800
Gen Condition
Dead Time Delay
SG1 3P
3086
Float
4
R W
Second
0.1 - 600
Gen Condition
Stable Undervoltage Pickup
SG1 3P
3088
Float
4
R W
Volt
10 - 99999
Gen Condition
Stable Undervoltage Dropout
SG1 3P
3090
Float
4
R W
Volt
10 - 99999
Gen Condition
Stable Overvoltage Pickup
SG1 3P
3092
Float
4
R W
Volt
10 - 99999
Gen Condition
Stable Overvoltage Dropout
SG1 3P
3094
Float
4
R W
Volt
10 - 99999
Gen Condition
Stable Underfrequency Pickup
SG1 3P
3096
Float
4
R W
Hertz
46 - 64
Gen Condition
Stable Underfrequency Dropout
SG1 3P
3098
Float
4
R W
Hertz
46 - 64
Gen Condition
Stable Overfrequency Pickup
SG1 3P
3100
Float
4
R W
Hertz
46 - 64
Gen Condition
Stable Overfrequency Dropout
SG1 3P
3102
Float
4
R W
Hertz
46 - 64
Gen Condition
Stable Time Delay
SG1 3P
3104
Float
4
R W
Second
0.1 - 600
Gen Condition
Fail Time Delay
SG1 3P
3106
Float
4
R W
Second
0.1 - 600
Gen Condition
Low-Line Scale
SG1 3P
3108
Float
4
R W
n/a
0.001 - 3
Gen Condition
Alternate Frequency Scale
SG1 3P
3110
Float
4
R W
n/a
0.001 - 100
Gen Condition
Dead Pickup
SG2 1P
3112
Float
4
R W
Volt
0 - 4800
Gen Condition
Dead Time Delay
SG2 1P
3114
Float
4
R W
Second
0.1 - 600
Gen Condition
Stable Undervoltage Pickup
SG2 1P
3116
Float
4
R W
Volt
10 - 99999
Gen Condition
Stable Undervoltage Dropout
SG2 1P
3118
Float
4
R W
Volt
10 - 99999
Gen Condition
Stable Overvoltage Pickup
SG2 1P
3120
Float
4
R W
Volt
10 - 99999
Gen Condition
Stable Overvoltage Dropout
SG2 1P
3122
Float
4
R W
Volt
10 - 99999
Gen Condition
Stable Underfrequency Pickup
SG2 1P
3124
Float
4
R W
Hertz
46 - 64
Gen Condition
Stable Underfrequency Dropout
SG2 1P
3126
Float
4
R W
Hertz
46 - 64