Basler Electric DGC-2020HD Modbus Protocol User Manual
Page 311
![background image](https://www.manualsdir.com/files/773959/content/doc311.png)
9469300991 Rev A
305
DGC-2020HD Modbus
™ Protocol
Legacy Register Table
Register
Description
Type
Units
Scaling
Factor
R/W
Range
46906
ATS Contact Input
Int32
n/a
n/a
RW -1 = None
0 = Input 1
1 = Input 2
2 = Input 3
3 = Input 4
4 = Input 5
5 = Input 6
6 = Input 7
7 = Input 8
8 = Input 9
9 = Input 10
10 = Input 11
11 = Input 12
12 = Input 13
13 = Input 14
14 = Input 15
15 = Input 16
46908
ATS Time Delay
Int32
Second
n/a
RW 0 – 300
46910
ATS Engine Running Only
Int32
n/a
n/a
RW 0 = Always
1 = While Engine Running Only
46912
Battle Override Contact Input
Int32
n/a
n/a
RW -1 = None
0 = Input 1
1 = Input 2
2 = Input 3
3 = Input 4
4 = Input 5
5 = Input 6
6 = Input 7
7 = Input 8
8 = Input 9
9 = Input 10
10 = Input 11
11 = Input 12
12 = Input 13
13 = Input 14
14 = Input 15
15 = Input 16
46914
Battle Override Time Delay
Int32
Second
n/a
RW 0 – 300
46916
Battle Override Engine Running Only
Int32
n/a
n/a
RW 0 = Always
1 = While Engine Running Only
46918
Low Coolant Level Contact Input
Int32
n/a
n/a
RW -1 = None
0 = Input 1
1 = Input 2
2 = Input 3
3 = Input 4
4 = Input 5
5 = Input 6
6 = Input 7
7 = Input 8
8 = Input 9
9 = Input 10
10 = Input 11
11 = Input 12
12 = Input 13
13 = Input 14
14 = Input 15
15 = Input 16
46920
Low Coolant Level Config Type
Int32
n/a
n/a
RW 0 = None
1 = Alarm
2 = Pre-Alarm
46922
Low Coolant Level Time Delay
Int32
Second
n/a
RW 0 – 300
46924
Low Coolant Level Engine Running Only
Int32
n/a
n/a
RW 0 = Always
1 = While Engine Running Only
46926
Battery Charge Failed Contact Input
Int32
n/a
n/a
RW -1 = None
0 = Input 1
1 = Input 2
2 = Input 3
3 = Input 4
4 = Input 5
5 = Input 6
6 = Input 7
7 = Input 8
8 = Input 9
9 = Input 10
10 = Input 11
11 = Input 12
12 = Input 13
13 = Input 14
14 = Input 15
15 = Input 16