Binary points – Basler Electric DGC-2020HD Modbus Protocol User Manual
Page 27
9469300991 Rev A
21
DGC-2020HD Modbus
™ Protocol
Default Register Table
Name
Description
Group Register Type Bytes R/W
Unit
Range
CEM 4 Contact Input 9 Contact Recognition
GG
0744
Uint32 4
R W n/a
Always=0
Engine Running=1
CEM 4 Contact Input 9 Alarm Configuration
GG
0746
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
CEM 4 Contact Input 9 Activation Delay
GG
0748
Uint32 4
R W Second
0 - 300
CEM 4 Contact Input
10
Contact Recognition
GG
0750
Uint32 4
R W n/a
Always=0
Engine Running=1
CEM 4 Contact Input
10
Alarm Configuration
GG
0752
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
CEM 4 Contact Input
10
Activation Delay
GG
0754
Uint32 4
R W Second
0 - 300
Auto Config Detect
Enable
GG
0756
Uint32 4
R W n/a
Disabled=0
Enabled=1
Auto Config Detect
Single-Phase Detection Threshold
GG
0758
Float
4
R W Volt
0 - 480
Auto Config Detect
Single-Phase Detection Gen Connection
GG
0760
Uint32 4
R W n/a
AB=0
AC=1
Auto Config Detect
Low-Line Detection Threshold
GG
0762
Float
4
R W Volt
0 - 480
Binary Points
Name
Description
Register Bit Type Bytes R/W
Range
Scale Factor Override
Alternate Frequency Override
1000
0
Uint16 2
R
False=0 True=1
Reserved
1000
1
System Data
Logic 0
1000
2
Uint16 2
R
False=0 True=1
System Data
Logic 1
1000
3
Uint16 2
R
False=0 True=1
Alarms
Real-Time Clock Alarm
1000
4
Uint16 2
R
False=0 True=1
Alarms
Date/Time Set Alarm
1000
5
Uint16 2
R
False=0 True=1
Alarms
Firmware Change Alarm
1000
6
Uint16 2
R
False=0 True=1
Alarms
Frequency Out-of-Range Alarm
1000
7
Uint16 2
R
False=0 True=1
Alarms
Ethernet Link 1 Lost Alarm
1000
8
Uint16 2
R
False=0 True=1
Alarms
Ethernet Link 2 Lost Alarm
1000
9
Uint16 2
R
False=0 True=1
Alarms
USB COM Alarm
1000
10 Uint16 2
R
False=0 True=1
Alarms
IRIG Sync Lost Alarm
1000
11 Uint16 2
R
False=0 True=1
Alarms
Logic = None Alarm
1000
12 Uint16 2
R
False=0 True=1
Alarms
No User Setting Alarm
1000
13 Uint16 2
R
False=0 True=1
Alarms
NTP Sync Lost Alarm
1000
14 Uint16 2
R
False=0 True=1
Alarms
uP Reset Alarm
1000
15 Uint16 2
R
False=0 True=1
Alarms
Programmable Alarm 1
1001
0
Uint16 2
R
False=0 True=1
Alarms
Programmable Alarm 2
1001
1
Uint16 2
R
False=0 True=1
Alarms
Programmable Alarm 3
1001
2
Uint16 2
R
False=0 True=1
Alarms
Programmable Alarm 4
1001
3
Uint16 2
R
False=0 True=1
Alarms
Programmable Alarm 5
1001
4
Uint16 2
R
False=0 True=1
Alarms
Programmable Alarm 6
1001
5
Uint16 2
R
False=0 True=1
Alarms
Programmable Alarm 7
1001
6
Uint16 2
R
False=0 True=1
Alarms
Programmable Alarm 8
1001
7
Uint16 2
R
False=0 True=1
Alarms
Programmable Alarm 9
1001
8
Uint16 2
R
False=0 True=1
Alarms
Programmable Alarm 10
1001
9
Uint16 2
R
False=0 True=1
Alarms
Programmable Alarm 11
1001
10 Uint16 2
R
False=0 True=1
Alarms
Programmable Alarm 12
1001
11 Uint16 2
R
False=0 True=1
Alarms
Programmable Alarm 13
1001
12 Uint16 2
R
False=0 True=1
Alarms
Programmable Alarm 14
1001
13 Uint16 2
R
False=0 True=1
Alarms
Programmable Alarm 15
1001
14 Uint16 2
R
False=0 True=1
Alarms
Programmable Alarm 16
1001
15 Uint16 2
R
False=0 True=1
Alarms
Unsupported Number of AEMs
1002
0
Uint16 2
R
False=0 True=1
Alarms
Unsupported Number of CEMs
1002
1
Uint16 2
R
False=0 True=1
Alarms
Logic Alarm
1002
2
Uint16 2
R
False=0 True=1
Alarms
Logic Pre-Alarm
1002
3
Uint16 2
R
False=0 True=1
Alarms
Global Sender Fail Alarm
1002
4
Uint16 2
R
False=0 True=1
Alarms
Clock Not Set Alarm
1002
5
Uint16 2
R
False=0 True=1
Alarms
Clock Battery Low Alarm
1002
6
Uint16 2
R
False=0 True=1
Alarm Report
Alarm Output
1002
7
Uint16 2
R
False=0 True=1
Pre-Alarm Report
Alarm Output
1002
8
Uint16 2
R
False=0 True=1
Contact Outputs
Output 1
1002
9
Uint16 2
R
False=0 True=1
Contact Outputs
Output 2
1002
10 Uint16 2
R
False=0 True=1
Contact Outputs
Output 3
1002
11 Uint16 2
R
False=0 True=1
Contact Outputs
Output 4
1002
12 Uint16 2
R
False=0 True=1
Contact Outputs
Output 5
1002
13 Uint16 2
R
False=0 True=1
Contact Outputs
Output 6
1002
14 Uint16 2
R
False=0 True=1
Contact Outputs
Output 7
1002
15 Uint16 2
R
False=0 True=1
Contact Outputs
Output 8
1003
0
Uint16 2
R
False=0 True=1
Contact Outputs
Output 9
1003
1
Uint16 2
R
False=0 True=1
Contact Outputs
Output 10
1003
2
Uint16 2