Basler Electric DGC-2020HD Modbus Protocol User Manual
Page 61

9469300991 Rev A
55
DGC-2020HD Modbus
™ Protocol
Default Register Table
Name
Description
Group Register Type Bytes R/W
Unit
Range
Sync
Source Volt Greater Than
Destination Volt
GG
2602
Uint32 4
R W n/a
Disabled=0
Enabled=1
Sync
Voltage Difference
GG
2604
Float
4
R W Percent
2 - 15
Sync
Synchronizer Type
GG
2606
Uint32 4
R W n/a
Anticipatory=0
Phase Lock Loop=1
Sync
Volt Error Gain
GG
2608
Float
4
R W n/a
0.001 - 1000
Sync
Speed Error Gain
GG
2610
Float
4
R W n/a
0.001 - 1000
Sync
Max Slip Control Limit
GG
2612
Float
4
R W Hertz
0 - 2
Sync
Min Slip Control Limit
GG
2614
Float
4
R W Hertz
0 - 2
Sync
Slip Frequency
GG
2616
Float
4
R W Hertz
0.01 - 0.5
Sync
Source Freq Greater Than
Destination Freq
GG
2618
Uint32 4
R W n/a
Disabled=0
Enabled=1
Sync
Closing Angle
GG
2620
Float
4
R W Degree
3 - 20
Sync
Sync Fail Activation Delay
GG
2622
Uint32 4
R W Millisecond 100 - 600000
Sync
Activation Delay
GG
2624
Uint32 4
R W Millisecond 100 - 800
Sync
Sync Mode
GG
2626
Uint32 4
R W n/a
Sync Run=0
Sync Check=1
Sync Only=2
Generator Breaker
Continuous Output
GG
2628
Uint32 4
R W n/a
Pulse=0
Continuous=1
Generator Breaker
Open Pulse Time
GG
2630
Uint32 4
R W Millisecond 10 - 10000
Generator Breaker
Close Pulse Time
GG
2632
Uint32 4
R W Millisecond 10 - 10000
Generator Breaker
Breaker Close Time
GG
2634
Uint32 4
R W Millisecond 0 - 1000
Generator Breaker
Configured
GG
2636
Uint32 4
R W n/a
Not Configured=0
Configured=1
Generator Breaker
Source Bus
GG
2638
Uint32 4
R W n/a
Gen=0
Bus 1=1
Bus 2=2
Generator Breaker
Destination Bus
GG
2640
Uint32 4
R W n/a
Gen=0
Bus 1=1
Bus 2=2
Generator Breaker
Transition Delay
GG
2642
Float
4
R W Second
0 - 10
Generator Breaker
External Status Change Action
GG
2644
Uint32 4
R W n/a
Ignore=0
Follow Always=1
Follow In Auto=2
Generator Breaker
Open Attempts
GG
2646
Uint32 4
R W n/a
1 - 20
Generator Breaker
Close Attempts
GG
2648
Uint32 4
R W n/a
1 - 20
Generator Breaker
Retry Delay
GG
2650
Uint32 4
R W Second
0 - 1200
Generator Breaker
Fail Output Config
GG
2652
Uint32 4
R W n/a
Retain=0
Remove=1
Mains Breaker
Continuous Output
GG
2654
Uint32 4
R W n/a
Pulse=0
Continuous=1
Mains Breaker
Open Pulse Time
GG
2656
Uint32 4
R W Millisecond 10 - 10000
Mains Breaker
Close Pulse Time
GG
2658
Uint32 4
R W Millisecond 10 - 10000
Mains Breaker
Breaker Close Time
GG
2660
Uint32 4
R W Millisecond 0 - 1000
Mains Breaker
Configured
GG
2662
Uint32 4
R W n/a
Not Configured=0
Configured=1
Mains Breaker
Source Bus
GG
2664
Uint32 4
R W n/a
Gen=0
Bus 1=1
Bus 2=2
Mains Breaker
Destination Bus
GG
2666
Uint32 4
R W n/a
Gen=0
Bus 1=1
Bus 2=2
Mains Breaker
Transition Delay
GG
2668
Float
4
R W Second
0 - 10
Mains Breaker
External Status Change Action
GG
2670
Uint32 4
R W n/a
Ignore=0
Follow Always=1
Follow In Auto=2
Mains Breaker
Open Attempts
GG
2672
Uint32 4
R W n/a
1 - 20
Mains Breaker
Close Attempts
GG
2674
Uint32 4
R W n/a
1 - 20
Mains Breaker
Retry Delay
GG
2676
Uint32 4
R W Second
0 - 1200
Mains Breaker
Fail Output Config
GG
2678
Uint32 4
R W n/a
Retain=0
Remove=1
Breaker Local Request
Generation
Transfer Enabled
GG
2680
Uint32 4
R W n/a
Disabled=0
Enabled=1
Breaker Local Request
Generation
Closed Transfer Enabled
GG
2682
Uint32 4
R W n/a
Open=0
Closed=1
Breaker Local Request
Generation
Reverse Rotation Mains Fail
Transfer Inhibit
GG
2684
Uint32 4
R W n/a
Disabled=0
Enabled=1
Breaker Local Request
Generation
Return Delay
GG
2686
Uint32 4
R W Second
0 - 1800
Breaker Local Request
Generation
Transfer Delay
GG
2688
Uint32 4
R W Second
0 - 300
Breaker Local Request
Generation
Max Transfer Time
GG
2690
Uint32 4
R W Second
10 - 120
Breaker Local Request
Generation
Max Parallel Time
GG
2692
Uint32 4
R W Decisecond 1 - 100000
Breaker Local Request
Generation
Alarm State Transfer To Mains
GG
2694
Uint32 4
R W n/a
Disabled=0
Enabled=1