Basler Electric DGC-2020HD Modbus Protocol User Manual
Page 269
9469300991 Rev A
263
DGC-2020HD Modbus
™ Protocol
Legacy Register Table
Register
Description
Type
Units
Scaling
Factor
R/W
Range
45556-57
AEM Input Threshold Pre-Alarm Bits Reg 3
Uint32 n/a
n/a
R
Bit 0 = Not Used
Bit 1 = Not Used
Bit 2 = Thermocouple 2 Under 2
Bit 3 = Thermocouple 2 Under 1
Bit 4 = Thermocouple 2 Over 2
Bit 5 = Thermocouple 2 Over 1
Bit 6 = Thermocouple 2 Out of Range
Bit 7 = Thermocouple 1 Under 2
Bit 8 = Thermocouple 1 Under 1
Bit 9 = Thermocouple 1 Over 2
Bit 10 = Thermocouple 1 Over 1
Bit 11 = Thermocouple 1 Out of Range
Bit 12 = RTD Input 8 Under 2
Bit 13 = RTD Input 8 Under 1
Bit 14 = RTD Input 8 Over 2
Bit 15 = RTD Input 8 Over 1
Bit 16 = RTD Input 8 Out of Range
Bit 17 = RTD Input 7 Under 2
Bit 18 = RTD Input 7 Under 1
Bit 19 = RTD Input 7 Over 2
Bit 20 = RTD Input 7 Over 1
Bit 21 = RTD Input 7 Out of Range
Bit 22 = RTD Input 6 Under 2
Bit 23 = RTD Input 6 Under 1
Bit 24 = RTD Input 6 Over 2
Bit 25 = RTD Input 6 Over 1
Bit 26 = RTD Input 6 Out of Range
Bit 27 = RTD Input 5 Under 2
Bit 28 = RTD Input 5 Under 1
Bit 29= RTD Input 5 Over 2
Bit 30 = RTD Input 5 Over 1
Bit 31 = RTD Input 5 Out of Range
45558-59
AEM Input Threshold Pre-Alarm Bits Reg 4
Uint32 n/a
n/a
R
Bit 0 = Not Used
Bit 1 = Not Used
Bit 2 = Not Used
Bit 3 = Not Used
Bit 4 = Not Used
Bit 5 = Not Used
Bit 6 = Not Used
Bit 7 = Not Used
Bit 8 = Not Used
Bit 9 = Not Used
Bit 10 = Not Used
Bit 11 = Not Used
Bit 12 = Not Used
Bit 13 = Not Used
Bit 14 = Not Used
Bit 15 = Not Used
Bit 16 = Not Used
Bit 17 = Not Used
Bit 18 = Not Used
Bit 19 = Not Used
Bit 20 = Not Used
Bit 21 = Not Used
Bit 22 = Not Used
Bit 23 = Not Used
Bit 24 = Not Used
Bit 25 = Not Used
Bit 26 = Not Used
Bit 27 = Not Used
Bit 28 = Analog Output 4 Out of Range
Bit 29 = Analog Output 3 Out of Range
Bit 30 = Analog Output 2 Out of Range
Bit 31 = Analog Output 1 Out of Range
45560
Analog Output 1 Metering Value
Int32
CentiUnit
Centi
R
(-100000000) – 99999900
45562
Analog Output 2 Metering Value
Int32
CentiUnit
Centi
R
(-100000000) – 99999900
45564
Analog Output 3 Metering Value
Int32
CentiUnit
Centi
R
(-100000000) – 99999900
45566
Analog Output 4 Metering Value
Int32
CentiUnit
Centi
R
(-100000000) – 99999900