Basler Electric DGC-2020HD Modbus Protocol User Manual

Page 269

background image

9469300991 Rev A

263

DGC-2020HD Modbus

™ Protocol

Legacy Register Table

Register

Description

Type

Units

Scaling

Factor

R/W

Range

45556-57

AEM Input Threshold Pre-Alarm Bits Reg 3

Uint32 n/a

n/a

R

Bit 0 = Not Used
Bit 1 = Not Used

Bit 2 = Thermocouple 2 Under 2
Bit 3 = Thermocouple 2 Under 1

Bit 4 = Thermocouple 2 Over 2

Bit 5 = Thermocouple 2 Over 1
Bit 6 = Thermocouple 2 Out of Range

Bit 7 = Thermocouple 1 Under 2
Bit 8 = Thermocouple 1 Under 1

Bit 9 = Thermocouple 1 Over 2
Bit 10 = Thermocouple 1 Over 1

Bit 11 = Thermocouple 1 Out of Range
Bit 12 = RTD Input 8 Under 2

Bit 13 = RTD Input 8 Under 1

Bit 14 = RTD Input 8 Over 2
Bit 15 = RTD Input 8 Over 1

Bit 16 = RTD Input 8 Out of Range
Bit 17 = RTD Input 7 Under 2

Bit 18 = RTD Input 7 Under 1
Bit 19 = RTD Input 7 Over 2

Bit 20 = RTD Input 7 Over 1

Bit 21 = RTD Input 7 Out of Range
Bit 22 = RTD Input 6 Under 2

Bit 23 = RTD Input 6 Under 1
Bit 24 = RTD Input 6 Over 2

Bit 25 = RTD Input 6 Over 1
Bit 26 = RTD Input 6 Out of Range

Bit 27 = RTD Input 5 Under 2

Bit 28 = RTD Input 5 Under 1
Bit 29= RTD Input 5 Over 2

Bit 30 = RTD Input 5 Over 1
Bit 31 = RTD Input 5 Out of Range

45558-59

AEM Input Threshold Pre-Alarm Bits Reg 4

Uint32 n/a

n/a

R

Bit 0 = Not Used
Bit 1 = Not Used

Bit 2 = Not Used
Bit 3 = Not Used

Bit 4 = Not Used
Bit 5 = Not Used

Bit 6 = Not Used

Bit 7 = Not Used
Bit 8 = Not Used

Bit 9 = Not Used
Bit 10 = Not Used

Bit 11 = Not Used
Bit 12 = Not Used

Bit 13 = Not Used

Bit 14 = Not Used
Bit 15 = Not Used

Bit 16 = Not Used
Bit 17 = Not Used

Bit 18 = Not Used
Bit 19 = Not Used

Bit 20 = Not Used

Bit 21 = Not Used
Bit 22 = Not Used

Bit 23 = Not Used
Bit 24 = Not Used

Bit 25 = Not Used
Bit 26 = Not Used

Bit 27 = Not Used
Bit 28 = Analog Output 4 Out of Range

Bit 29 = Analog Output 3 Out of Range

Bit 30 = Analog Output 2 Out of Range
Bit 31 = Analog Output 1 Out of Range

45560

Analog Output 1 Metering Value

Int32

CentiUnit

Centi

R

(-100000000) – 99999900

45562

Analog Output 2 Metering Value

Int32

CentiUnit

Centi

R

(-100000000) – 99999900

45564

Analog Output 3 Metering Value

Int32

CentiUnit

Centi

R

(-100000000) – 99999900

45566

Analog Output 4 Metering Value

Int32

CentiUnit

Centi

R

(-100000000) – 99999900