Basler Electric DGC-2020HD Modbus Protocol User Manual
Page 72
66
9469300991 Rev A
Default Register Table
DGC-2020HD Modbus
™ Protocol
Name
Description
Group Register
Type
Bytes R/W
Unit
Range
RS485 Settings
Baud Rate
GG
6600
Uint32
4
R W n/a
1200 Baud=1200
2400 Baud=2400
4800 Baud=4800
9600 Baud=9600
19200 Baud=19200
38400 Baud=38400
57600 Baud=57600
115200 Baud=115200
RS485 Settings
Parity
GG
6602
Uint32
4
R W n/a
Even Parity=0
Odd Parity=1
No Parity=2
RS485 Settings
Bits Per Character
GG
6604
Uint32
4
R W n/a
8-Bits=8
7-Bits=7
RS485 Settings
Stop Bits
GG
6606
Uint32
4
R W n/a
1 Stop Bit=1
2 Stop Bits=2
Ethernet 0 Settings
Subnet Mask
GG
6608
IP
Address
4
R W n/a
n/a
Ethernet 0 Settings
Gateway Address
GG
6610
IP
Address
4
R W n/a
n/a
Ethernet 0 Settings
Use DHCP
GG
6612
Uint32
4
R W n/a
Off=0
On=1
Ethernet 0 Settings
Active IP
GG
6614
IP
Address
4
R
n/a
n/a
Ethernet 0 Settings
Active Gateway
GG
6616
IP
Address
4
R
n/a
n/a
Ethernet 0 Settings
Active Subnet
GG
6618
IP
Address
4
R
n/a
n/a
Ethernet 1 Settings
Subnet Mask
GG
6620
IP
Address
4
R W n/a
n/a
Ethernet 1 Settings
Gateway Address
GG
6622
IP
Address
4
R W n/a
n/a
Ethernet 1 Settings
Use DHCP
GG
6624
Uint32
4
R W n/a
Off=0
On=1
Ethernet 1 Settings
Active IP
GG
6626
IP
Address
4
R
n/a
n/a
Ethernet 1 Settings
Active Gateway
GG
6628
IP
Address
4
R
n/a
n/a
Ethernet 1 Settings
Active Subnet
GG
6630
IP
Address
4
R
n/a
n/a
Modbus
Modbus Ethernet Unit ID
GG
6632
Uint16
2
R W n/a
1 - 247
Modbus
Modbus Serial Unit ID
GG
6633
Uint16
2
R W n/a
1 - 247
Reserved
6634-39
Engine Source
Speed Mode
GG
6640
Uint32
4
R W n/a
Magnetic Pickup=1
Gen Freq=2
MPU/Gen Freq=3
Engine Source
Flywheel Teeth
GG
6642
Uint32
4
R W n/a
1 - 500
Engine Source
Speed Sender Fail Time Delay
GG
6644
Uint32
4
R W Second 0 - 300