Basler Electric DGC-2020HD Modbus Protocol User Manual
Page 189

9469300991 Rev A
183
DGC-2020HD Modbus
™ Protocol
Default Register Table
Name
Description
Group Register Type Bytes R/W
Unit
Range
51-3
Curve Index
SG2 1P 23606
Uint32 4
R W n/a
S1=0
S2=1
L1=2
L2=3
D=4
M=5
I1=6
I2=7
V1=8
V2=9
E1=10
E2=11
A=12
B=13
C=14
G=15
F=16
46=17
P=18
51-3
Direction
SG2 1P 23608
Uint32 4
R W n/a
Forward=0
Reverse=1
Non-Directional=2
51-3
Use Instantaneous Reset
SG2 1P 23610
Uint32 4
R W n/a
Integrating=0
Instantaneous=1
51-3
Constant TD
SG2 1P 23612
Float
4
R W n/a
0 - 9.9
51-3
Constant A
SG2 1P 23614
Float
4
R W n/a
0 - 600
51-3
Constant B
SG2 1P 23616
Float
4
R W n/a
0 - 25
51-3
Constant C
SG2 1P 23618
Float
4
R W n/a
0 - 1
51-3
Constant N
SG2 1P 23620
Float
4
R W n/a
0.5 - 2.5
51-3
Constant R
SG2 1P 23622
Float
4
R W n/a
0 - 30
51-3
Voltage Restraint Setpoint
SG2 1P 23624
Float
4
R W Volt
30 - 250
51-3
Voltage Restraint Mode
SG2 1P 23626
Uint32 4
R W n/a
Disabled=0
Control=1
Restraint=2
51-3
Alarm Configuration
SG2 1P 23628
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
51-3
Low-Line Scale
SG2 1P 23630
Float
4
R W n/a
0.001 - 3
51-3
Voltage Restraint Source
SG2 1P 23632
Uint32 4
R W n/a
Gen=0
Bus 1=1
Bus 2=2
51-3
Constant Q
SG2 1P 23634
Float
4
R W n/a
0.1 - 10
51-3
Mode
SG2 3P 23636
Uint32 4
R W n/a
Disabled=0
IA=1
IB=2
IC=3
Imax=4
3I0=5
I2=6
IG=7
I1=8
51-3
Source
SG2 3P 23638
Uint32 4
R W n/a
Gen=0
Bus 1=1
Bus 2=2
51-3
Pickup
SG2 3P 23640
Float
4
R W Amp
0.9 - 7.75
51-3
Curve Index
SG2 3P 23642
Uint32 4
R W n/a
S1=0
S2=1
L1=2
L2=3
D=4
M=5
I1=6
I2=7
V1=8
V2=9
E1=10
E2=11
A=12
B=13
C=14
G=15
F=16
46=17
P=18
51-3
Direction
SG2 3P 23644
Uint32 4
R W n/a
Forward=0
Reverse=1
Non-Directional=2
51-3
Use Instantaneous Reset
SG2 3P 23646
Uint32 4
R W n/a
Integrating=0
Instantaneous=1
51-3
Constant TD
SG2 3P 23648
Float
4
R W n/a
0 - 9.9