Basler Electric DGC-2020HD Modbus Protocol User Manual
Page 214

208
9469300991 Rev A
Default Register Table
DGC-2020HD Modbus
™ Protocol
Name
Description
Group Register Type Bytes R/W
Unit
Range
Config Protection 1
Threshold 3 Type
GG
24764
Int32
4
R W n/a
Disabled=0
Over=1
Under=2
Config Protection 1
Threshold 3 Pickup
GG
24766
Float
4
R W n/a
-999999 - 999999
Config Protection 1
Threshold 3 Activation Delay
GG
24768
Float
4
R W Second
0 - 300
Config Protection 1
Threshold 3 Alarm Configuration GG
24770
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
Config Protection 1
Threshold 4 Type
GG
24772
Int32
4
R W n/a
Disabled=0
Over=1
Under=2
Config Protection 1
Threshold 4 Pickup
GG
24774
Float
4
R W n/a
-999999 - 999999
Config Protection 1
Threshold 4 Activation Delay
GG
24776
Float
4
R W Second
0 - 300
Config Protection 1
Threshold 4 Alarm Configuration GG
24778
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
Config Protection 1
Low-Line Scale Current
GG
24780
Float
4
R W n/a
0.001 - 3
Config Protection 1
Low-Line Scale Voltage
GG
24782
Float
4
R W n/a
0.001 - 3
Config Protection 1
Label
GG
24784
String 16
R W n/a
0 - 16
Config Protection 2
Parameter Selection
GG
24786
Int32
4
R W n/a
No Parameter=0
Oil Pressure=1
Coolant Temp=2
Battery Volts=3
RPM=4
Fuel Level=5
Gen Hz=6
Gen VAB=7
Gen VBC=8
Gen VCA=9
Gen Vavg LL=10
Gen VAN=11
Gen VBN=12
Gen VCN=13
Gen Vavg LN=14
Bus 1 Hz=15
Bus 1 VAB=16
Bus 1 VBC=17
Bus 1 VCA=18
Bus 1 Vavg LL=19
Bus 1 VA=20
Bus 1 VB=21
Bus 1 VC=22
Bus 1 Vavg LN=23
Bus 2 Hz=24
Bus 2 VAB=25
Bus 2 VBC=26
Bus 2 VCA=27
Bus 2 Vavg LL=28
Bus 2 VAN=29
Bus 2 VBN=30
Bus 2 VCN=31
Bus 2 Vavg LN=32
Gen PF=33
Bus 1 PF=34
Bus 2 PF=35
Gen Pos kWh=36
Gen Neg kWh=37
Bus 1 Pos kWh=38
Bus 1 Neg kWh=39
Bus 2 Pos kWh=40
Bus 2 Neg kWh=41
Gen IA=42
Gen IB=43
Gen IC=44
Gen I Avg=45
Bus 1 IA=46
Bus 1 IB=47
Bus 1 IC=48
Bus 1 Iavg=49
Bus 2 IAN=50
Bus 2 IBN=51
Bus 2 ICN=52
Bus 2 Iavg=53
IG=54
I Aux=55
Gen kW A=56
Gen kW B=57
Gen kW C=58
Gen kW Total=59
Bus 1 kW A=60
Bus 1 kW B=61