Basler Electric DGC-2020HD Modbus Protocol User Manual
Page 179
9469300991 Rev A
173
DGC-2020HD Modbus
™ Protocol
Default Register Table
Name
Description
Group Register Type Bytes R/W
Unit
Range
51-1
Mode
SG3 3P 23132
Uint32 4
R W n/a
Disabled=0
IA=1
IB=2
IC=3
Imax=4
3I0=5
I2=6
IG=7
I1=8
51-1
Source
SG3 3P 23134
Uint32 4
R W n/a
Gen=0
Bus 1=1
Bus 2=2
51-1
Pickup
SG3 3P 23136
Float
4
R W Amp
0.9 - 7.75
51-1
Curve Index
SG3 3P 23138
Uint32 4
R W n/a
S1=0
S2=1
L1=2
L2=3
D=4
M=5
I1=6
I2=7
V1=8
V2=9
E1=10
E2=11
A=12
B=13
C=14
G=15
F=16
46=17
P=18
51-1
Direction
SG3 3P 23140
Uint32 4
R W n/a
Forward=0
Reverse=1
Non-Directional=2
51-1
Use Instantaneous Reset
SG3 3P 23142
Uint32 4
R W n/a
Integrating=0
Instantaneous=1
51-1
Constant TD
SG3 3P 23144
Float
4
R W n/a
0 - 9.9
51-1
Constant A
SG3 3P 23146
Float
4
R W n/a
0 - 600
51-1
Constant B
SG3 3P 23148
Float
4
R W n/a
0 - 25
51-1
Constant C
SG3 3P 23150
Float
4
R W n/a
0 - 1
51-1
Constant N
SG3 3P 23152
Float
4
R W n/a
0.5 - 2.5
51-1
Constant R
SG3 3P 23154
Float
4
R W n/a
0 - 30
51-1
Voltage Restraint Setpoint
SG3 3P 23156
Float
4
R W Volt
30 - 250
51-1
Voltage Restraint Mode
SG3 3P 23158
Uint32 4
R W n/a
Disabled=0
Control=1
Restraint=2
51-1
Alarm Configuration
SG3 3P 23160
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
51-1
Low-Line Scale
SG3 3P 23162
Float
4
R W n/a
0.001 - 3
51-1
Voltage Restraint Source
SG3 3P 23164
Uint32 4
R W n/a
Gen=0
Bus 1=1
Bus 2=2
51-1
Constant Q
SG3 3P 23166
Float
4
R W n/a
0.1 - 10
51-2
Mode
SG0 1P 23168
Uint32 4
R W n/a
Disabled=0
IA=1
IB=2
IC=3
Imax=4
3I0=5
I2=6
IG=7
I1=8
51-2
Source
SG0 1P 23170
Uint32 4
R W n/a
Gen=0
Bus 1=1
Bus 2=2
51-2
Pickup
SG0 1P 23172
Float
4
R W Amp
0.9 - 7.75