Metering – Basler Electric DGC-2020HD Modbus Protocol User Manual
Page 250

244
9469300991 Rev A
Legacy Register Table
DGC-2020HD Modbus
™ Protocol
Register
Description
Type
Units
Scaling Factor R/W
Range
44540
High Fuel Level Pre-Alarm Threshold
Int32
Percent
n/a
RW
0 - 150
44542
High Fuel Level Pre-Alarm Enable
Int32
n/a
n/a
RW
0 = Disable
1 = Enable
44544
High Fuel Level Pre-Alarm Activation Delay
Int32
Second
n/a
RW
0 - 30
44546
Low Fuel Level Pre-Alarm Enable
Uint32 n/a
n/a
RW
0 = Disable
1 = Enable
44548
Low Fuel Level Pre-Alarm Threshold
Uint32 Percent
n/a
RW
10 - 100
44550
Low Battery Pre-Alarm Enable
Uint32 n/a
n/a
RW
0 = Disable
1 = Enable
44552
Low Battery Pre-Alarm Threshold
Uint32 DeciVolt
Deci
RW
60 - 280
44554
Low Battery Pre-Alarm Activation Delay
Uint32 Second
n/a
RW
1 - 10
44556
Weak Battery Pre-Alarm Enable
Uint32 n/a
n/a
RW
0 = Disable
1 = Enable
44558
Weak Battery Pre-Alarm Threshold
Uint32 DeciVolt
Deci
RW
40 - 280
44560
Weak Battery Pre-Alarm Activation Delay
Uint32 Second
Deci
RW
0 - 100
44562
Battery Overvoltage Pre-Alarm Enable
Uint32 n/a
n/a
RW
0 = Disable
1 = Enable
44564
Low Oil Press. Pre-Alarm Enable
Uint32 n/a
n/a
RW
0 = Disable
1 = Enable
44566
Low Oil Press. Pre-Alarm Threshold
Uint32 PSI
Deci
RW
29 - 1500
44568
Metric Low Oil Press. Pre-Alarm Threshold
Int32
kPa
Deci
RW
20 - 10345
44570-73
Reserved
Uint32 n/a
n/a
RW
0 = Disable
1 = Enable
44574
ECU Comms Fail Pre-Alarm Enable
Int32
n/a
n/a
RW
0 = Disable
1 = Enable
44576
Active DTC Pre-Alarm Enable
Int32
n/a
n/a
RW
0 = Disable
1 = Enable
44578
Maintenance Interval Pre-Alarm Enable
Uint32 n/a
n/a
RW
0 = Disable
1 = Enable
44580
Maintenance Interval Pre-Alarm Threshold
Uint32 Hour
n/a
RW
0 - 5000
44582
Speed Sender Fail Activation Delay
Int32
Second
n/a
RW
0 - 300
44584
ECU Low Coolant Level Alarm Enable
Uint32 n/a
n/a
RW
0 = Disable
1 = Enable
44586
ECU Low Coolant Level Alarm Threshold
Uint32 Percent
n/a
RW
1 - 99
44588
ECU Low Coolant Level Pre-Alarm Enable
Uint32 n/a
n/a
RW
0 = Disable
1 = Enable
44590
ECU Low Coolant Level Pre-Alarm Threshold
Uint32 Percent
n/a
RW
1 - 99
44592
Battery Overvoltage Alarm Threshold
Int32
DeciVolt
Deci
RW
120 - 320
44594-627 Reserved
44628
Intergenset Comm Failure Pre-alarm Enable
Int32
n/a
n/a
RW
0 = Disable
1 = Enable
44630
AVR Bias Output Limit Pre-alarm Activation Delay
Int32
Second
n/a
RW
1 - 15
44632
AVR Bias Output Limit Pre-alarm Enable
Int32
n/a
n/a
RW
0 = Disable
1 = Enable
44634
GOV Bias Output Limit Pre-alarm Activation Delay
Int32
Second
n/a
RW
1 - 15
44636
GOV Bias Output Limit Pre-alarm Enable
Int32
n/a
n/a
RW
0 = Disable
1 = Enable
44638
ID Missing Pre-alarm Enable
Int32
n/a
n/a
RW
0 = Disable
1 = Enable
44640
ID Repeat Pre-alarm Enable
Int32
n/a
n/a
RW
0 = Disable
1 = Enable
44642
CEM Comm Failure Pre-alarm Enable
Int32
n/a
n/a
RW
0 = Disable
1 = Enable
44644
AEM Comm Failure Pre-alarm Enable
Int32
n/a
n/a
RW
0 = Disable
1 = Enable
44646
Reserved
44648
Low Oil Pressure Alarm (metric pressure units is Bar)
Int32
Bar
Deci
RW
2 - 103
44650
Low Oil Pressure Pre-Alarm (metric pressure units is Bar)
Int32
Bar
Deci
RW
2 - 103
44652
Sync Fail Pre-alarm Enable
Int32
n/a
n/a
RW
0 = Disable
1 = Enable
44654
Breaker Close Fail Pre-Alarm Enable
Int32
n/a
n/a
RW
0 = Disable
1 = Enable
44656
Breaker Open Fail Pre-Alarm Enable
Int32
n/a
n/a
RW
0 = Disable
1 = Enable
44658
Breaker Close Fail Pre-Alarm Monitor
Int32
n/a
n/a
RW
0 = Transitions Only
1 = Always
44660
Breaker Open Fail Pre-Alarm Monitor
Int32
n/a
n/a
RW
0 = Transitions Only
1 = Always
44662
Reverse Rotation Pre-Alarm Enable
Uint32 n/a
n/a
RW
0 = Disable
1 = Enable
Metering
Register
Description
Type
Units
Scaling
Factor
R/W
Range
44750
Gen VAB Metering
Int32
Volt
n/a
R
(-2147483648) - 2147483647
44752
Gen VBC Metering
Int32
Volt
n/a
R
(-2147483648) - 2147483647