Basler Electric DGC-2020HD Modbus Protocol User Manual
Page 219

9469300991 Rev A
213
DGC-2020HD Modbus
™ Protocol
Default Register Table
Name
Description
Group Register Type Bytes R/W
Unit
Range
AEM 3 Analog Input 4=339
AEM 3 Analog Input 5=340
AEM 3 Analog Input 6=341
AEM 3 Analog Input 7=342
AEM 3 Analog Input 8=343
AEM 3 RTD Input 1=344
AEM 3 RTD Input 2=345
AEM 3 RTD Input 3=346
AEM 3 RTD Input 4=347
AEM 3 RTD Input 5=348
AEM 3 RTD Input 6=349
AEM 3 RTD Input 7=350
AEM 3 RTD Input 8=351
AEM 3 TC Input 1=352
AEM 3 TC Input 2=353
AEM 4 Analog Input 1=354
AEM 4 Analog Input 2=355
AEM 4 Analog Input 3=356
AEM 4 Analog Input 4=357
AEM 4 Analog Input 5=358
AEM 4 Analog Input 6=359
AEM 4 Analog Input 7=360
AEM 4 Analog Input 8=361
AEM 4 RTD Input 1=362
AEM 4 RTD Input 2=363
AEM 4 RTD Input 3=364
AEM 4 RTD Input 4=365
AEM 4 RTD Input 5=366
AEM 4 RTD Input 6=367
AEM 4 RTD Input 7=368
AEM 4 RTD Input 8=369
AEM 4 TC Input 1=370
AEM 4 TC Input 2=371
AVR Output=372
GOV Output=373
LS Output=374
Config Protection 3
Hysteresis
GG
24838
Float
4
R W Percent
0 - 100
Config Protection 3
Arming Delay
GG
24840
Float
4
R W Second
0 - 300
Config Protection 3
Threshold 1 Type
GG
24842
Int32
4
R W n/a
Disabled=0
Over=1
Under=2
Config Protection 3
Threshold 1 Pickup
GG
24844
Float
4
R W n/a
-999999 - 999999
Config Protection 3
Threshold 1 Activation Delay
GG
24846
Float
4
R W Second
0 - 300
Config Protection 3
Threshold 1 Alarm Configuration GG
24848
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
Config Protection 3
Threshold 2 Type
GG
24850
Int32
4
R W n/a
Disabled=0
Over=1
Under=2
Config Protection 3
Threshold 2 Pickup
GG
24858
Float
4
R W n/a
-999999 - 999999
Config Protection 3
Threshold 2 Activation Delay
GG
24860
Float
4
R W Second
0 - 300
Config Protection 3
Threshold 2 Alarm Configuration GG
24862
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
Config Protection 3
Threshold 3 Type
GG
24864
Int32
4
R W n/a
Disabled=0
Over=1
Under=2
Config Protection 3
Threshold 3 Pickup
GG
24866
Float
4
R W n/a
-999999 - 999999
Config Protection 3
Threshold 3 Activation Delay
GG
24868
Float
4
R W Second
0 - 300
Config Protection 3
Threshold 3 Alarm Configuration GG
24870
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
Config Protection 3
Threshold 4 Type
GG
24872
Int32
4
R W n/a
Disabled=0
Over=1
Under=2
Config Protection 3
Threshold 4 Pickup
GG
24874
Float
4
R W n/a
-999999 - 999999
Config Protection 3
Threshold 4 Activation Delay
GG
24876
Float
4
R W Second
0 - 300
Config Protection 3
Threshold 4 Alarm Configuration GG
24878
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
Config Protection 3
Low-Line Scale Current
GG
24880
Float
4
R W n/a
0.001 - 3
Config Protection 3
Low-Line Scale Voltage
GG
24882
Float
4
R W n/a
0.001 - 3
Config Protection 3
Label
GG
24884
String 16
R W n/a
0 - 16
Config Protection 4
Parameter Selection
GG
24886
Int32
4
R W n/a
No Parameter=0
Oil Pressure=1
Coolant Temp=2
Battery Volts=3
RPM=4
Fuel Level=5
Gen Hz=6