Pulse outputs, Bus condition detection – Basler Electric DGC-2020HD Modbus Protocol User Manual
Page 239

9469300991 Rev A
233
DGC-2020HD Modbus
™ Protocol
Legacy Register Table
Register
Description
Type
Units
Scaling Factor
R/W
Range
42418
Remote Speed Bias Source
Int32
n/a
n/a
RW
0 = None
1 = Local Analog Input 1
2 = Local Analog Input 2
3 = Local Analog Input 3
4 = Local Analog Input 4
5 = AEM 1 Analog Input 1
6 = AEM 1 Analog Input 2
7 = AEM 1 Analog Input 3
8 = AEM 1 Analog Input 4
9 = AEM 1 Analog Input 5
10 = AEM 1 Analog Input 6
11 = AEM 1 Analog Input 7
12 = AEM 1 Analog Input 8
13 = AEM 2 Analog Input 1
14 = AEM 2 Analog Input 2
15 = AEM 2 Analog Input 3
16 = AEM 2 Analog Input 4
17 = AEM 2 Analog Input 5
18 = AEM 2 Analog Input 6
19 = AEM 2 Analog Input 7
20 = AEM 2 Analog Input 8
21 = AEM 3 Analog Input 1
22 = AEM 3 Analog Input 2
23 = AEM 3 Analog Input 3
24 = AEM 3 Analog Input 4
25 = AEM 3 Analog Input 5
26 = AEM 3 Analog Input 6
27 = AEM 3 Analog Input 7
28 = AEM 3 Analog Input 8
29 = AEM 4 Analog Input 1
30 = AEM 4 Analog Input 2
31 = AEM 4 Analog Input 3
32 = AEM 4 Analog Input 4
33 = AEM 4 Analog Input 5
34 = AEM 4 Analog Input 6
35 = AEM 4 Analog Input 7
36 = AEM 4 Analog Input 8
42420-23
Reserved
42424
Load Sharing Aux Input Source
Int32
n/a
n/a
RW
0 = Local Aux Input
1 = System Manager
42426
kW Ramp Status
Int32
n/a
n/a
R
0 - 2
42428
kvar Ramp Status
Int32
n/a
n/a
R
0 - 2
Pulse Outputs
Register
Description
Type
Units
Scaling Factor
R/W
Range
42500
AVR Correction Pulse Width
Int32
Decisecond
Deci
RW
0 - 999
42502
AVR Correction Pulse Interval
Int32
Decisecond
Deci
RW
0 - 999
42504
AVR Bias Contact Type
Int32
n/a
n/a
RW
0 = Continuous
1 = Proportional
42506
Reserved
42508
Governor Correction Pulse Width
Int32
Decisecond
Deci
RW
0 - 999
42510
Governor Correction Pulse Interval
Int32
Decisecond
Deci
RW
0 - 999
42512
Governor Bias Contact Type
Int32
Decisecond
Deci
RW
0 = Continuous
1 = Proportional
Bus Condition Detection
Register
Description
Type
Units
Scaling Factor
R/W
Range
42750
Gen Sensing Dead Bus Pickup
Int32
Volt
n/a
RW
0 - 4800
42752
Gen Sensing Dead Bus Time Delay
Int32
Decisecond
Deci
RW
1 - 6000
42754
Reserved
42756
Gen Sensing Stable Undervoltage Pickup
Int32
Volt
n/a
RW
10 - 99999
42758
Gen Sensing Stable Undervoltage Dropout
Int32
Volt
n/a
RW
10 - 99999
42760
Gen Sensing Stable Overvoltage
Int32
Volt
n/a
RW
10 - 99999
42762
Gen Sensing Stable Overvoltage Dropout
Int32
Volt
n/a
RW
10 - 99999
42764
Gen Sensing Stable Underfrequency Pickup
Int32
CentiHertz
Centi
RW
4600 - 6400
42766
Gen Sensing Stable Underfrequency Dropout
Int32
CentiHertz
Centi
RW
4600 - 6400
42768
Gen Sensing Stable Overfrequency Pickup
Int32
CentiHertz
Centi
RW
4600 - 6400
42770
Gen Sensing Stable Overfrequency Dropout
Int32
CentiHertz
Centi
RW
4600 - 6400
42772
Gen Sensing Fail Time Delay
Int32
Decisecond
Deci
RW
1 - 6000
42774
Gen Sensing Stable Time Delay
Int32
Decisecond
Deci
RW
1 - 6000
42776
Reserved
42778
Bus Sensing Dead Bus Pickup
Int32
Volt
n/a
RW
0 - 4800
42780
Bus Sensing Dead Bus Time Delay
Int32
Decisecond
Deci
RW
1 - 6000
42782
Reserved