Basler Electric DGC-2020HD Modbus Protocol User Manual
Page 20

14
9469300991 Rev A
Default Register Table
DGC-2020HD Modbus
™ Protocol
Name
Description
Group Register Type Bytes R/W
Unit
Range
Low-Line Override
Contact Input
GG
0320
Uint32 4
R W n/a
None=0
Input 1=1
Input 2=2
Input 3=3
Input 4=4
Input 5=5
Input 6=6
Input 7=7
Input 8=8
Input 9=9
Input 10=10
Input 11=11
Input 12=12
Input 13=13
Input 14=14
Input 15=15
Input 16=16
Low-Line Override
Contact Recognition
GG
0322
Uint32 4
R W n/a
Always=0
Engine Running=1
Low-Line Override
Alarm Configuration
GG
0324
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
Low-Line Override
Activation Delay
GG
0326
Uint32 4
R W Second
0 - 300
Single-Phase AC
Override
Contact Input
GG
0328
Uint32 4
R W n/a
None=0
Input 1=1
Input 2=2
Input 3=3
Input 4=4
Input 5=5
Input 6=6
Input 7=7
Input 8=8
Input 9=9
Input 10=10
Input 11=11
Input 12=12
Input 13=13
Input 14=14
Input 15=15
Input 16=16
Single-Phase AC
Override
Contact Recognition
GG
0330
Uint32 4
R W n/a
Always=0
Engine Running=1
Single-Phase AC
Override
Alarm Configuration
GG
0332
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
Single-Phase AC
Override
Activation Delay
GG
0334
Uint32 4
R W Second
0 - 300
Battery Charger Fail
Contact Input
GG
0336
Uint32 4
R W n/a
None=0
Input 1=1
Input 2=2
Input 3=3
Input 4=4
Input 5=5
Input 6=6
Input 7=7
Input 8=8
Input 9=9
Input 10=10
Input 11=11
Input 12=12
Input 13=13
Input 14=14
Input 15=15
Input 16=16
Battery Charger Fail
Contact Recognition
GG
0338
Uint32 4
R W n/a
Always=0
Engine Running=1
Battery Charger Fail
Alarm Configuration
GG
0340
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
Battery Charger Fail
Activation Delay
GG
0342
Uint32 4
R W Second
0 - 300