Basler Electric DGC-2020HD Modbus Protocol User Manual
Page 23

9469300991 Rev A
17
DGC-2020HD Modbus
™ Protocol
Default Register Table
Name
Description
Group Register Type Bytes R/W
Unit
Range
Contact Input 3
Contact Recognition
GG
0432
Uint32 4
R W n/a
Always=0
Engine Running=1
Contact Input 3
Alarm Configuration
GG
0434
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
Contact Input 3
Activation Delay
GG
0436
Uint32 4
R W Second
0 - 300
Contact Input 4
Contact Recognition
GG
0438
Uint32 4
R W n/a
Always=0
Engine Running=1
Contact Input 4
Alarm Configuration
GG
0440
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
Contact Input 4
Activation Delay
GG
0442
Uint32 4
R W Second
0 - 300
Contact Input 5
Contact Recognition
GG
0444
Uint32 4
R W n/a
Always=0
Engine Running=1
Contact Input 5
Alarm Configuration
GG
0446
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
Contact Input 5
Activation Delay
GG
0448
Uint32 4
R W Second
0 - 300
Contact Input 6
Contact Recognition
GG
0450
Uint32 4
R W n/a
Always=0
Engine Running=1
Contact Input 6
Alarm Configuration
GG
0452
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
Contact Input 6
Activation Delay
GG
0454
Uint32 4
R W Second
0 - 300
Contact Input 7
Contact Recognition
GG
0456
Uint32 4
R W n/a
Always=0
Engine Running=1
Contact Input 7
Alarm Configuration
GG
0458
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
Contact Input 7
Activation Delay
GG
0460
Uint32 4
R W Second
0 - 300
Contact Input 8
Contact Recognition
GG
0462
Uint32 4
R W n/a
Always=0
Engine Running=1
Contact Input 8
Alarm Configuration
GG
0464
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
Contact Input 8
Activation Delay
GG
0466
Uint32 4
R W Second
0 - 300
Contact Input 9
Contact Recognition
GG
0468
Uint32 4
R W n/a
Always=0
Engine Running=1
Contact Input 9
Alarm Configuration
GG
0470
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
Contact Input 9
Activation Delay
GG
0472
Uint32 4
R W Second
0 - 300
Contact Input 10
Contact Recognition
GG
0474
Uint32 4
R W n/a
Always=0
Engine Running=1
Contact Input 10
Alarm Configuration
GG
0476
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
Contact Input 10
Activation Delay
GG
0478
Uint32 4
R W Second
0 - 300
Contact Input 11
Contact Recognition
GG
0480
Uint32 4
R W n/a
Always=0
Engine Running=1
Contact Input 11
Alarm Configuration
GG
0482
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
Contact Input 11
Activation Delay
GG
0484
Uint32 4
R W Second
0 - 300
Contact Input 12
Contact Recognition
GG
0486
Uint32 4
R W n/a
Always=0
Engine Running=1
Contact Input 12
Alarm Configuration
GG
0488
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
Contact Input 12
Activation Delay
GG
0490
Uint32 4
R W Second
0 - 300
Contact Input 13
Contact Recognition
GG
0492
Uint32 4
R W n/a
Always=0
Engine Running=1
Contact Input 13
Alarm Configuration
GG
0494
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
Contact Input 13
Activation Delay
GG
0496
Uint32 4
R W Second
0 - 300
Contact Input 14
Contact Recognition
GG
0498
Uint32 4
R W n/a
Always=0
Engine Running=1
Contact Input 14
Alarm Configuration
GG
0500
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
Contact Input 14
Activation Delay
GG
0502
Uint32 4
R W Second
0 - 300
Contact Input 15
Contact Recognition
GG
0504
Uint32 4
R W n/a
Always=0
Engine Running=1
Contact Input 15
Alarm Configuration
GG
0506
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
Contact Input 15
Activation Delay
GG
0508
Uint32 4
R W Second
0 - 300