Legacy Register Table
DGC-2020HD Modbus
™ Protocol
Register
Description
Type
Units
Scaling Factor
R/W
Range
44396
3 Phase Reverse Power Alarm Configuration
Uint32
n/a
n/a
RW
0 = None
1 = Alarm
2 = Pre-Alarm
3 = Status Only
44398
Reserved
44400
1 Phase Reverse Power Pickup
Int32
DeciPercent
Deci
RW
50 - 500
44402
1 Phase Reverse Power Activation Delay
Uint32
Decisecond
Deci
RW
0 - 300
44404
1 Phase Reverse Power Alarm Configuration
Uint32
n/a
n/a
RW
0 = None
1 = Alarm
2 = Pre-Alarm
3 = Status Only
44406
Reserved
44408
3 Phase Loss of Excitation Pickup
Int32
DeciPercent
Deci
RW
(-1500) - 0
44410
3 Phase Loss of Excitation Activation Delay
Uint32
Decisecond
Deci
RW
0 - 300
44412
3 Phase Loss of Excitation Alarm Configuration
Uint32
n/a
n/a
RW
0 = None
1 = Alarm
2 = Pre-Alarm
3 = Status Only
44414
Reserved
44416
1 Phase Loss of Excitation Pickup
Int32
DeciPercent
Deci
RW
(-1500) - 0
44418
1 Phase Loss of Excitation Activation Delay
Uint32
Decisecond
Deci
RW
0 - 300
44420
1 Phase Loss of Excitation Alarm Configuration
Uint32
n/a
n/a
RW
0 = None
1 = Alarm
2 = Pre-Alarm
3 = Status Only
44422
Reserved
44424
3 Phase Overcurrent Reset Type (51-1)
Int32
n/a
n/a
RW
0 = Instantaneous
1 = Integrating
44426
1 Phase Overcurrent Reset Type (51-1)
Int32
n/a
n/a
RW
0 = Instantaneous
1 = Integrating
44428
3 Phase Overcurrent Reset Type (51-2)
Int32
n/a
n/a
RW
0 = Instantaneous
1 = Integrating
44430
1 Phase Overcurrent Reset Type (51-2)
Int32
n/a
n/a
RW
0 = Instantaneous
1 = Integrating
44432
51-1 Curve Constant A
Float
n/a
n/a
RW
0 - 600
44434
51-1 Curve Constant B
Float
n/a
n/a
RW
0 - 25
44436
51-1 Curve Constant C
Float
n/a
n/a
RW
0 - 1
44438
51-1 Curve Constant N
Float
n/a
n/a
RW
0.5 - 2.5
44440
51-1 Curve Constant R
Float
n/a
n/a
RW
0 - 30
44442
51-2 Curve Constant A
Float
n/a
n/a
RW
0 - 600
44444
51-2 Curve Constant B
Float
n/a
n/a
RW
0 - 25
44446
51-2 Curve Constant C
Float
n/a
n/a
RW
0 - 1
44448
51-2 Curve Constant N
Float
n/a
n/a
RW
0.5 - 2.5
44450
51-2 Curve Constant R
Float
n/a
n/a
RW
0 - 30
44452
3 Phase Overcurrent Pickup
(51-3)
Uint32
CentiAmp
Centi
RW
18 - 775
44454
3 Phase Overcurrent Time Dial (51-3)
Uint32
DeciUnit
Deci
RW
0 - 72000
44456
3 Phase Overcurrent Curve
(51-3)
Uint32
n/a
n/a
RW
0 = S1 Curve
1 = S2 Curve
2 = L1 Curve
3 = L2 Curve
4 = D Curve
5 = M Curve
6 = I1 Curve
7 = I2 Curve
8 = V1 Curve
9 = V2 Curve
10 = E1 Curve
11 = E2 Curve
12 = A Curve
13 = B Curve
14 = C Curve
15 = G Curve
16 = F Curve
17 = Programmable
44458
3 Phase Overcurrent Alarm Configuration (51-3)
Uint32
n/a
n/a
RW
0 = None
1 = Alarm
2 = Pre-Alarm
3 = Status Only
44460
1 Phase Overcurrent Pickup
(51-3)
Uint32
CentiAmp
Centi
RW
18 - 775
44462
1 Phase Overcurrent Time Dial (51-3)
Uint32
DeciUnit
Deci
RW
0 - 72000