Basler Electric DGC-2020HD Modbus Protocol User Manual
Page 296
290
9469300991 Rev A
Legacy Register Table
DGC-2020HD Modbus
™ Protocol
Register
Description
Type
Units
Scaling
Factor
R/W
Range
46338
AEM Input 1 Over 1 Alarm Type
Int32
n/a
n/a
RW 0 = Status Only
1 = Pre-Alarm
2 = Alarm
46340
AEM Input 1 Over 2 Alarm Type
Int32
n/a
n/a
RW 0 = Status Only
1 = Pre-Alarm
2 = Alarm
46342
AEM Input 1 Under 1 Alarm Type
Int32
n/a
n/a
RW 0 = Status Only
1 = Pre-Alarm
2 = Alarm
46344
AEM Input 1 Under 2 Alarm Type
Int32
n/a
n/a
RW 0 = Status Only
1 = Pre-Alarm
2 = Alarm
46346
AEM Input 1 Out of Range Alarm Type
Int32
n/a
n/a
RW 0 = Status Only
1 = Pre-Alarm
2 = Alarm
46348
AEM Input 2 Max Voltage
Int32
DeciVolt
Deci
RW 0 - 100
46350
AEM Input 2 Max Current
Int32
Milliamp x
10
Deci
RW 40 - 200
46352
AEM Input 2 Min Voltage
Int32
DeciVolt
Deci
RW 0 - 100
46354
AEM Input 2 Min Current
Int32
Milliamp x
10
Deci
RW 40 - 200
46356
AEM Input 2 Param Max
Int32
Centi Unit
Centi
RW (-100000000) – 99999900
46358
AEM Input 2 Param Min
Int32
Centi Unit
Centi
RW (-100000000) – 99999900
46360
AEM Input 2 Hysteresis
Int32
Deci
Percent
Deci
RW 0 – 1000
46362
AEM Input 2 Arming Delay
Int32
Second
n/a
RW 0 – 300
46364
AEM Input 2 Threshold 1 Activation Delay
Int32
Second
n/a
RW 0 – 300
46366
AEM Input 2 Threshold 2 Activation Delay
Int32
Second
n/a
RW 0 – 300
46368
AEM Input 2 Over 1 Threshold
Int32
Centi Unit
Centi
RW (-100000000) – 99999900
46370
AEM Input 2 Over 2 Threshold
Int32
Centi Unit
Centi
RW (-100000000) – 99999900
46372
AEM Input 2 Under 1 Threshold
Int32
Centi Unit
Centi
RW (-100000000) – 99999900
46374
AEM Input 2 Under 2 Threshold
Int32
Centi Unit
Centi
RW (-100000000) – 99999900
46376
AEM Input 2 Over 1 Alarm Type
Int32
n/a
n/a
RW 0 = Status Only
1 = Pre-Alarm
2 = Alarm
46378
AEM Input 2 Over 2 Alarm Type
Int32
n/a
n/a
RW 0 = Status Only
1 = Pre-Alarm
2 = Alarm
46380
AEM Input 2 Under 1 Alarm Type
Int32
n/a
n/a
RW 0 = Status Only
1 = Pre-Alarm
2 = Alarm
46382
AEM Input 2 Under 2 Alarm Type
Int32
n/a
n/a
RW 0 = Status Only
1 = Pre-Alarm
2 = Alarm
46384
AEM Input 2 Out of Range Alarm Type
Int32
n/a
n/a
RW 0 = Status Only
1 = Pre-Alarm
2 = Alarm
46386
AEM Input 3 Max Voltage
Int32
DeciVolt
Deci
RW 0 - 100
46388
AEM Input 3 Max Current
Int32
Milliamp x
10
Deci
RW 40 - 200
46390
AEM Input 3 Min Voltage
Int32
DeciVolt
Deci
RW 0 - 100
46392
AEM Input 3 Min Current
Int32
Milliamp x
10
Deci
RW 40 - 200
46394
AEM Input 3 Param Max
Int32
Centi Unit
Centi
RW (-100000000) – 99999900
46396
AEM Input 3 Param Min
Int32
Centi Unit
Centi
RW (-100000000) – 99999900
46398
AEM Input 3 Hysteresis
Int32
Deci
Percent
Deci
RW 0 – 1000
46400
AEM Input 3 Arming Delay
Int32
Second
n/a
RW 0 – 300
46402
AEM Input 3 Threshold 1 Activation Delay
Int32
Second
n/a
RW 0 – 300
46404
AEM Input 3 Threshold 2 Activation Delay
Int32
Second
n/a
RW 0 – 300
46406
AEM Input 3 Over 1 Threshold
Int32
Centi Unit
Centi
RW (-100000000) – 99999900
46408
AEM Input 3 Over 2 Threshold
Int32
Centi Unit
Centi
RW (-100000000) – 99999900
46410
AEM Input 3 Under 1 Threshold
Int32
Centi Unit
Centi
RW (-100000000) – 99999900
46412
AEM Input 3 Under 2 Threshold
Int32
Centi Unit
Centi
RW (-100000000) – 99999900
46414
AEM Input 3 Over 1 Alarm Type
Int32
n/a
n/a
RW 0 = Status Only
1 = Pre-Alarm
2 = Alarm
46416
AEM Input 3 Over 2 Alarm Type
Int32
n/a
n/a
RW 0 = Status Only
1 = Pre-Alarm
2 = Alarm
46418
AEM Input 3 Under 1 Alarm Type
Int32
n/a
n/a
RW 0 = Status Only
1 = Pre-Alarm
2 = Alarm
46420
AEM Input 3 Under 2 Alarm Type
Int32
n/a
n/a
RW 0 = Status Only
1 = Pre-Alarm
2 = Alarm
46422
AEM Input 3 Out of Range Alarm Type
Int32
n/a
n/a
RW 0 = Status Only
1 = Pre-Alarm
2 = Alarm