Alarms – Basler Electric DGC-2020HD Modbus Protocol User Manual
Page 249
![background image](https://www.manualsdir.com/files/773959/content/doc249.png)
9469300991 Rev A
243
DGC-2020HD Modbus
™ Protocol
Legacy Register Table
Register
Description
Type
Units
Scaling Factor
R/W
Range
44464
1 Phase Overcurrent Curve
(51-3)
Uint32
n/a
n/a
RW
0 = S1 Curve
1 = S2 Curve
2 = L1 Curve
3 = L2 Curve
4 = D Curve
5 = M Curve
6 = I1 Curve
7 = I2 Curve
8 = V1 Curve
9 = V2 Curve
10 = E1 Curve
11 = E2 Curve
12 = A Curve
13 = B Curve
14 = C Curve
15 = G Curve
16 = F Curve
17 = Programmable
44466
1 Phase Overcurrent Alarm Configuration (51-3)
Uint32
n/a
n/a
RW
0 = None
1 = Alarm
2 = Pre-Alarm
3 = Status Only
44468
Overcurrent Low Line Scale Factor (51-3)
Float
n/a
n/a
RW
0.001 - 3
44470
3 Phase Overcurrent Reset Type (51-3)
Int32
n/a
n/a
RW
0 = Instantaneous
1 = Integrating
44472
1 Phase Overcurrent Reset Type (51-3)
Int32
n/a
n/a
RW
0 = Instantaneous
1 = Integrating
44474
51-3 Curve Constant A
Float
n/a
n/a
RW
0 - 600
44476
51-3 Curve Constant B
Float
n/a
n/a
RW
0 - 25
44478
51-3 Curve Constant C
Float
n/a
n/a
RW
0 - 1
44480
51-3 Curve Constant N
Float
n/a
n/a
RW
0.5 - 2.5
44482
51-3 Curve Constant R
Float
n/a
n/a
RW
0 - 30
44484
78 Vector Shift Alarm Config
Uint32
n/a
n/a
RW
0 = None
1 = Alarm
2 = Pre-Alarm
3 = Status Only
44486
78 Vector Shift Pickup
Int32
Degree
n/a
RW
2 - 90
44488
78 Open Mains Breaker on Trip
Int32
n/a
n/a
RW
0 = Disable
1 = Enable
44490
81 ROCOF Alarm Config
Uint32
n/a
n/a
RW
0 = None
1 = Alarm
2 = Pre-Alarm
3 = Status Only
44492
81 ROCOF Pickup
Uint32
Hz/Second
Deci
RW
2 - 100
44494
81 ROCOF Activation Delay
Uint32
Second
Milli
RW
0 - 10000
44496
81 ROCOF Open Mains Breaker on Trip
Int32
n/a
n/a
RW
0 = Disable
1 = Enable
44498
Alternate Frequency Scale Factor
Float
n/a
n/a
RW
0.001 - 100
Alarms
Register
Description
Type
Units
Scaling Factor R/W
Range
44500
High Coolant Temp Alarm Enable
Uint32 n/a
n/a
RW
0 = Disable
1 = Enable
44502
High Coolant Temp Alarm Threshold
Uint32 Deg F
n/a
RW
100 - 280
44504
Metric High Coolant Temp Alarm Threshold
Int32
Deg C
n/a
RW
38 - 138
44506
High Coolant Temp Alarm Activation Delay
Uint32 Second
n/a
RW
0 - 150
44508
Low Oil Press. Alarm Enable
Uint32 n/a
n/a
RW
0 = Disable
1 = Enable
44510
Low Oil Press. Alarm Threshold
Uint32 PSI
Deci
RW
29 - 1500
44512
Metric Low Oil Press. Alarm Threshold
Uint32 kPa
Deci
RW
200 - 10345
44514
Low Oil Press. Alarm Arming Delay
Uint32 Second
n/a
RW
5 - 60
44516
Overspeed Alarm Enable
Uint32 n/a
n/a
RW
0 = Disable
1 = Enable
44518
Overspeed Alarm Threshold
Uint32 Percent
n/a
RW
105 - 140
44520
Overspeed Alarm Activation Delay
Uint32 Millisecond Milli
RW
0 - 500
44522
Low Fuel Level Alarm Enable
Uint32 n/a
n/a
RW
0 = Disable
1 = Enable
44524
Low Fuel Level Alarm Threshold
Uint32 Percent
n/a
RW
0 - 100
44526
Low Fuel Level Alarm Activation Delay
Int32
Second
n/a
RW
0 - 30
44528
High Coolant Temp Pre-Alarm Enable
Uint32 n/a
n/a
RW
0 = Disable
1 = Enable
44530
High Coolant Temp Pre-Alarm Threshold
Uint32 Deg F
n/a
RW
100 - 280
44532
Metric High Coolant Temp Pre-Alarm Threshold
Int32
Deg C
n/a
RW
38 - 138
44534
Low Coolant Temp Pre-Alarm Enable
Uint32 n/a
n/a
RW
0 = Disable
1 = Enable
44536
Low Coolant Temp Pre-Alarm Threshold
Uint32 Deg F
n/a
RW
35 - 151
44538
Metric Low Coolant Temp Pre-Alarm Threshold
Int32
Deg C
n/a
RW
2 - 66