™ Protocol
Default Register Table
Name
Description
Group Register Type Bytes R/W
Unit
Range
Low Coolant Level
Contact Input
GG
0344
Uint32 4
R W n/a
None=0
Input 1=1
Input 2=2
Input 3=3
Input 4=4
Input 5=5
Input 6=6
Input 7=7
Input 8=8
Input 9=9
Input 10=10
Input 11=11
Input 12=12
Input 13=13
Input 14=14
Input 15=15
Input 16=16
Low Coolant Level
Contact Recognition
GG
0346
Uint32 4
R W n/a
Always=0
Engine Running=1
Low Coolant Level
Alarm Configuration
GG
0348
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
Low Coolant Level
Activation Delay
GG
0350
Uint32 4
R W Second
0 - 300
Fuel Leak Detect
Contact Input
GG
0352
Uint32 4
R W n/a
None=0
Input 1=1
Input 2=2
Input 3=3
Input 4=4
Input 5=5
Input 6=6
Input 7=7
Input 8=8
Input 9=9
Input 10=10
Input 11=11
Input 12=12
Input 13=13
Input 14=14
Input 15=15
Input 16=16
Fuel Leak Detect
Contact Recognition
GG
0354
Uint32 4
R W n/a
Always=0
Engine Running=1
Fuel Leak Detect
Alarm Configuration
GG
0356
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
Fuel Leak Detect
Activation Delay
GG
0358
Uint32 4
R W Second
0 - 300
Emergency Stop
Contact Input
GG
0360
Uint32 4
R W n/a
None=0
Input 1=1
Input 2=2
Input 3=3
Input 4=4
Input 5=5
Input 6=6
Input 7=7
Input 8=8
Input 9=9
Input 10=10
Input 11=11
Input 12=12
Input 13=13
Input 14=14
Input 15=15
Input 16=16
Emergency Stop
Contact Recognition
GG
0362
Uint32 4
R W n/a
Always=0
Engine Running=1
Emergency Stop
Alarm Configuration
GG
0364
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
Emergency Stop
Activation Delay
GG
0366
Uint32 4
R W Second
0 - 300