Basler Electric DGC-2020HD Modbus Protocol User Manual
Page 183

9469300991 Rev A
177
DGC-2020HD Modbus
™ Protocol
Default Register Table
Name
Description
Group Register Type Bytes R/W
Unit
Range
51-2
Curve Index
SG2 1P 23318
Uint32 4
R W n/a
S1=0
S2=1
L1=2
L2=3
D=4
M=5
I1=6
I2=7
V1=8
V2=9
E1=10
E2=11
A=12
B=13
C=14
G=15
F=16
46=17
P=18
51-2
Direction
SG2 1P 23320
Uint32 4
R W n/a
Forward=0
Reverse=1
Non-Directional=2
51-2
Use Instantaneous Reset
SG2 1P 23322
Uint32 4
R W n/a
Integrating=0
Instantaneous=1
51-2
Constant TD
SG2 1P 23324
Float
4
R W n/a
0 - 9.9
51-2
Constant A
SG2 1P 23326
Float
4
R W n/a
0 - 600
51-2
Constant B
SG2 1P 23328
Float
4
R W n/a
0 - 25
51-2
Constant C
SG2 1P 23330
Float
4
R W n/a
0 - 1
51-2
Constant N
SG2 1P 23332
Float
4
R W n/a
0.5 - 2.5
51-2
Constant R
SG2 1P 23334
Float
4
R W n/a
0 - 30
51-2
Voltage Restraint Setpoint
SG2 1P 23336
Float
4
R W Volt
30 - 250
51-2
Voltage Restraint Mode
SG2 1P 23338
Uint32 4
R W n/a
Disabled=0
Control=1
Restraint=2
51-2
Alarm Configuration
SG2 1P 23340
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
51-2
Low-Line Scale
SG2 1P 23342
Float
4
R W n/a
0.001 - 3
51-2
Voltage Restraint Source
SG2 1P 23344
Uint32 4
R W n/a
Gen=0
Bus 1=1
Bus 2=2
51-2
Constant Q
SG2 1P 23346
Float
4
R W n/a
0.1 - 10
51-2
Mode
SG2 3P 23348
Uint32 4
R W n/a
Disabled=0
IA=1
IB=2
IC=3
Imax=4
3I0=5
I2=6
IG=7
I1=8
51-2
Source
SG2 3P 23350
Uint32 4
R W n/a
Gen=0
Bus 1=1
Bus 2=2
51-2
Pickup
SG2 3P 23352
Float
4
R W Amp
0.9 - 7.75
51-2
Curve Index
SG2 3P 23354
Uint32 4
R W n/a
S1=0
S2=1
L1=2
L2=3
D=4
M=5
I1=6
I2=7
V1=8
V2=9
E1=10
E2=11
A=12
B=13
C=14
G=15
F=16
46=17
P=18
51-2
Direction
SG2 3P 23356
Uint32 4
R W n/a
Forward=0
Reverse=1
Non-Directional=2
51-2
Use Instantaneous Reset
SG2 3P 23358
Uint32 4
R W n/a
Integrating=0
Instantaneous=1
51-2
Constant TD
SG2 3P 23360
Float
4
R W n/a
0 - 9.9