Basler Electric DGC-2020HD Modbus Protocol User Manual
Page 222
216
9469300991 Rev A
Default Register Table
DGC-2020HD Modbus
™ Protocol
Name
Description
Group Register Type Bytes R/W
Unit
Range
AEM 3 TC Input 1=352
AEM 3 TC Input 2=353
AEM 4 Analog Input 1=354
AEM 4 Analog Input 2=355
AEM 4 Analog Input 3=356
AEM 4 Analog Input 4=357
AEM 4 Analog Input 5=358
AEM 4 Analog Input 6=359
AEM 4 Analog Input 7=360
AEM 4 Analog Input 8=361
AEM 4 RTD Input 1=362
AEM 4 RTD Input 2=363
AEM 4 RTD Input 3=364
AEM 4 RTD Input 4=365
AEM 4 RTD Input 5=366
AEM 4 RTD Input 6=367
AEM 4 RTD Input 7=368
AEM 4 RTD Input 8=369
AEM 4 TC Input 1=370
AEM 4 TC Input 2=371
AVR Output=372
GOV Output=373
LS Output=374
Config Protection 4
Hysteresis
GG
24888
Float
4
R W Percent
0 - 100
Config Protection 4
Arming Delay
GG
24890
Float
4
R W Second
0 - 300
Config Protection 4
Threshold 1 Type
GG
24892
Int32
4
R W n/a
Disabled=0
Over=1
Under=2
Config Protection 4
Threshold 1 Pickup
GG
24894
Float
4
R W n/a
-999999 - 999999
Config Protection 4
Threshold 1 Activation Delay
GG
24896
Float
4
R W Second
0 - 300
Config Protection 4
Threshold 1 Alarm Configuration GG
24898
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
Config Protection 4
Threshold 2 Type
GG
24900
Int32
4
R W n/a
Disabled=0
Over=1
Under=2
Config Protection 4
Threshold 2 Pickup
GG
24908
Float
4
R W n/a
-999999 - 999999
Config Protection 4
Threshold 2 Activation Delay
GG
24910
Float
4
R W Second
0 - 300
Config Protection 4
Threshold 2 Alarm Configuration GG
24912
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
Config Protection 4
Threshold 3 Type
GG
24914
Int32
4
R W n/a
Disabled=0
Over=1
Under=2
Config Protection 4
Threshold 3 Pickup
GG
24916
Float
4
R W n/a
-999999 - 999999
Config Protection 4
Threshold 3 Activation Delay
GG
24918
Float
4
R W Second
0 - 300
Config Protection 4
Threshold 3 Alarm Configuration GG
24920
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
Config Protection 4
Threshold 4 Type
GG
24922
Int32
4
R W n/a
Disabled=0
Over=1
Under=2
Config Protection 4
Threshold 4 Pickup
GG
24924
Float
4
R W n/a
-999999 - 999999
Config Protection 4
Threshold 4 Activation Delay
GG
24926
Float
4
R W Second
0 - 300
Config Protection 4
Threshold 4 Alarm Configuration GG
24928
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
Config Protection 4
Low-Line Scale Current
GG
24930
Float
4
R W n/a
0.001 - 3
Config Protection 4
Low-Line Scale Voltage
GG
24932
Float
4
R W n/a
0.001 - 3
Config Protection 4
Label
GG
24934
String 16
R W n/a
0 - 16
Config Protection 5
Parameter Selection
GG
24936
Int32
4
R W n/a
No Parameter=0
Oil Pressure=1
Coolant Temp=2
Battery Volts=3
RPM=4
Fuel Level=5
Gen Hz=6
Gen VAB=7
Gen VBC=8
Gen VCA=9
Gen Vavg LL=10
Gen VAN=11
Gen VBN=12
Gen VCN=13
Gen Vavg LN=14
Bus 1 Hz=15
Bus 1 VAB=16
Bus 1 VBC=17
Bus 1 VCA=18
Bus 1 Vavg LL=19