Communication, Protection – Basler Electric DGC-2020HD Modbus Protocol User Manual
Page 245
9469300991 Rev A
239
DGC-2020HD Modbus
™ Protocol
Legacy Register Table
Communication
Register
Description
Type
Units
Scaling Factor
R/W
Range
44008-16
Reserved
44018
Modem Inter Dialout Activation Delay
Int32
Second
n/a
RW
0 = 15
1 = 30
2 = 60
3 = 120
44020
Modem Pager Buffer Limit
Int32
n/a
n/a
RW
0 = 80 Chars
1 = 120 Chars
2 = 160 Chars
3 = 200 Chars
44022
Modem Pager Coms Data Format
Int32
n/a
n/a
RW
0 = 8 bit, no parity
1 = 7 bit, even parity
44024-30
Reserved
44032
CANBus Enable
Int32
n/a
n/a
RW
0 = Disable
1 = Enable
44034
DTC Enable
Int32
n/a
n/a
RW
0 = Disable
1 = Enable
44036
Rings for Modem Answer
Int32
n/a
n/a
RW
1 - 9
44038
Modem Offline Delay
Int32
Minute
n/a
RW
1 - 240
44040
Modbus Baud Rate
Uint32
n/a
n/a
RW
1200 = 1200 Baud
2400 = 2400 Baud
4800 = 4800 Baud
9600 = 9600 Baud
19200 = 19200 Baud
38400 = 38400 Baud
57600 = 57600 Baud
115200 = 115200 Baud
44042
Modbus Parity
Int32
n/a
n/a
RW
0 = Even Parity
1 = Odd Parity
2 = No Parity
44044
Modbus Address
Int32
n/a
n/a
RW
1 - 247
44046-49
Reserved
44050
DHCP Enabled
Uint32
n/a
n/a
R
0 = Disabled
1 = Enabled
44052-56
Reserved
44058
CEM-2020 Enable
Int32
n/a
n/a
RW
0 = Disable
1 = Enable
44060
Reserved
44062
AEM-2020 Enable
Int32
n/a
n/a
RW
0 = Disable
1 = Enable
44064
CEM Outputs
Int32
n/a
n/a
RW
0 = 18 Outputs
1 = 24 Outputs
44066-67
Reserved
44068
Active IP Address
Uint32
n/a
n/a
R
0 - 4294967295
44070
Gateway IP Address
Uint32
n/a
n/a
R
0 - 4294967295
44072
Subnet Mask
Uint32
n/a
n/a
R
0 - 4294967295
Protection
Register
Description
Type
Units
Scaling Factor
R/W
Range
44250
3 Phase Overcurrent Pickup
(51-1)
Uint32
CentiAmp
Centi
RW
18 - 775
44252
3 Phase Overcurrent Time Dial (51-1)
Uint32
DeciUnit
Deci
RW
0 - 72000
44254
3 Phase Overcurrent Curve
(51-1)
Uint32
n/a
n/a
RW
0 = S1 Curve
1 = S2 Curve
2 = L1 Curve
3 = L2 Curve
4 = D Curve
5 = M Curve
6 = I1 Curve
7 = I2 Curve
8 = V1 Curve
9 = V2 Curve
10 = E1 Curve
11 = E2 Curve
12 = A Curve
13 = B Curve
14 = C Curve
15 = G Curve
16 = F Curve
17 = Programmable
44256
3 Phase Overcurrent Alarm Configuration (51-1)
Uint32
n/a
n/a
RW
0 = None
1 = Alarm
2 = Pre-Alarm
3 = Status Only