Basler Electric DGC-2020HD Modbus Protocol User Manual
Page 28
![background image](https://www.manualsdir.com/files/773959/content/doc028.png)
22
9469300991 Rev A
Default Register Table
DGC-2020HD Modbus
™ Protocol
Name
Description
Register Bit Type Bytes R/W
Range
Contact Outputs
Output 11
1003
3
Uint16 2
R
False=0 True=1
Contact Outputs
Output 12
1003
4
Uint16 2
R
False=0 True=1
Contact Outputs
Preheat Prelube Relay
1003
5
Uint16 2
R
False=0 True=1
Contact Outputs
Fuel Solenoid Relay
1003
6
Uint16 2
R
False=0 True=1
Contact Outputs
Master Start Relay
1003
7
Uint16 2
R
False=0 True=1
Virtual Switch
Virtual Switch 1
1003
8
Uint16 2
R
False=0 True=1
Virtual Switch
Virtual Switch 2
1003
9
Uint16 2
R
False=0 True=1
Virtual Switch
Virtual Switch 3
1003
10 Uint16 2
R
False=0 True=1
Virtual Switch
Virtual Switch 4
1003
11 Uint16 2
R
False=0 True=1
Virtual Switch
Virtual Switch 5
1003
12 Uint16 2
R
False=0 True=1
Virtual Switch
Virtual Switch 6
1003
13 Uint16 2
R
False=0 True=1
Buzzer
Alarm Silence Active
1003
14 Uint16 2
R
False=0 True=1
Power Meter
PF Lagging
1003
15 Uint16 2
R
False=0 True=1
Power Meter 2
PF Lagging
1004
0
Uint16 2
R
False=0 True=1
Power Meter 3
PF Lagging
1004
1
Uint16 2
R
False=0 True=1
27P-1
Block
1004
2
Uint16 2
R
False=0 True=1
27P-1
Pickup
1004
3
Uint16 2
R
False=0 True=1
27P-1
Trip
1004
4
Uint16 2
R
False=0 True=1
27P-1
Pre-Alarm
1004
5
Uint16 2
R
False=0 True=1
27P-1
Alarm
1004
6
Uint16 2
R
False=0 True=1
27P-2
Block
1004
7
Uint16 2
R
False=0 True=1
27P-2
Pickup
1004
8
Uint16 2
R
False=0 True=1
27P-2
Trip
1004
9
Uint16 2
R
False=0 True=1
27P-2
Pre-Alarm
1004
10 Uint16 2
R
False=0 True=1
27P-2
Alarm
1004
11 Uint16 2
R
False=0 True=1
27P-3
Block
1004
12 Uint16 2
R
False=0 True=1
27P-3
Pickup
1004
13 Uint16 2
R
False=0 True=1
27P-3
Trip
1004
14 Uint16 2
R
False=0 True=1
27P-3
Pre-Alarm
1004
15 Uint16 2
R
False=0 True=1
27P-3
Alarm
1005
0
Uint16 2
R
False=0 True=1
27P-4
Block
1005
1
Uint16 2
R
False=0 True=1
27P-4
Pickup
1005
2
Uint16 2
R
False=0 True=1
27P-4
Trip
1005
3
Uint16 2
R
False=0 True=1
27P-4
Pre-Alarm
1005
4
Uint16 2
R
False=0 True=1
27P-4
Alarm
1005
5
Uint16 2
R
False=0 True=1
27P-5
Block
1005
6
Uint16 2
R
False=0 True=1
27P-5
Pickup
1005
7
Uint16 2
R
False=0 True=1
27P-5
Trip
1005
8
Uint16 2
R
False=0 True=1
27P-5
Pre-Alarm
1005
9
Uint16 2
R
False=0 True=1
27P-5
Alarm
1005
10 Uint16 2
R
False=0 True=1
27P-6
Block
1005
11 Uint16 2
R
False=0 True=1
27P-6
Pickup
1005
12 Uint16 2
R
False=0 True=1
27P-6
Trip
1005
13 Uint16 2
R
False=0 True=1
27P-6
Pre-Alarm
1005
14 Uint16 2
R
False=0 True=1
27P-6
Alarm
1005
15 Uint16 2
R
False=0 True=1
59P-1
Block
1006
0
Uint16 2
R
False=0 True=1
59P-1
Pickup
1006
1
Uint16 2
R
False=0 True=1
59P-1
Trip
1006
2
Uint16 2
R
False=0 True=1
59P-1
Pre-Alarm
1006
3
Uint16 2
R
False=0 True=1
59P-1
Alarm
1006
4
Uint16 2
R
False=0 True=1
59P-2
Block
1006
5
Uint16 2
R
False=0 True=1
59P-2
Pickup
1006
6
Uint16 2
R
False=0 True=1
59P-2
Trip
1006
7
Uint16 2
R
False=0 True=1
59P-2
Pre-Alarm
1006
8
Uint16 2
R
False=0 True=1
59P-2
Alarm
1006
9
Uint16 2
R
False=0 True=1
59P-3
Block
1006
10 Uint16 2
R
False=0 True=1
59P-3
Pickup
1006
11 Uint16 2
R
False=0 True=1
59P-3
Trip
1006
12 Uint16 2
R
False=0 True=1
59P-3
Pre-Alarm
1006
13 Uint16 2
R
False=0 True=1
59P-3
Alarm
1006
14 Uint16 2
R
False=0 True=1
59P-4
Block
1006
15 Uint16 2
R
False=0 True=1
59P-4
Pickup
1007
0
Uint16 2
R
False=0 True=1
59P-4
Trip
1007
1
Uint16 2
R
False=0 True=1
59P-4
Pre-Alarm
1007
2
Uint16 2
R
False=0 True=1
59P-4
Alarm
1007
3
Uint16 2
R
False=0 True=1
59P-5
Block
1007
4
Uint16 2
R
False=0 True=1
59P-5
Pickup
1007
5
Uint16 2
R
False=0 True=1
59P-5
Trip
1007
6
Uint16 2
R
False=0 True=1
59P-5
Pre-Alarm
1007
7
Uint16 2
R
False=0 True=1
59P-5
Alarm
1007
8
Uint16 2
R
False=0 True=1
59P-6
Block
1007
9
Uint16 2
R
False=0 True=1
59P-6
Pickup
1007
10 Uint16 2
R
False=0 True=1
59P-6
Trip
1007
11 Uint16 2
R
False=0 True=1
59P-6
Pre-Alarm
1007
12 Uint16 2
R
False=0 True=1
59P-6
Alarm
1007
13 Uint16 2
R
False=0 True=1