Basler Electric DGC-2020HD Modbus Protocol User Manual
Page 210

204
9469300991 Rev A
Default Register Table
DGC-2020HD Modbus
™ Protocol
Name
Description
Group Register Type Bytes R/W
Unit
Range
78-1
Alarm Configuration
SG2
24630
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
78-1
Mode
SG3
24632
Uint32 4
R W n/a
Disabled=0
Enabled=1
78-1
Source
SG3
24634
Uint32 4
R W n/a
Gen=0
Bus 1=1
Bus 2=2
78-1
Pickup
SG3
24636
Float
4
R W Degree
2 - 90
78-1
Alarm Configuration
SG3
24638
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
78-2
Mode
SG0
24640
Uint32 4
R W n/a
Disabled=0
Enabled=1
78-2
Source
SG0
24642
Uint32 4
R W n/a
Gen=0
Bus 1=1
Bus 2=2
78-2
Pickup
SG0
24644
Float
4
R W Degree
2 - 90
78-2
Alarm Configuration
SG0
24646
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
78-2
Mode
SG1
24648
Uint32 4
R W n/a
Disabled=0
Enabled=1
78-2
Source
SG1
24650
Uint32 4
R W n/a
Gen=0
Bus 1=1
Bus 2=2
78-2
Pickup
SG1
24652
Float
4
R W Degree
2 - 90
78-2
Alarm Configuration
SG1
24654
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
78-2
Mode
SG2
24656
Uint32 4
R W n/a
Disabled=0
Enabled=1
78-2
Source
SG2
24658
Uint32 4
R W n/a
Gen=0
Bus 1=1
Bus 2=2
78-2
Pickup
SG2
24660
Float
4
R W Degree
2 - 90
78-2
Alarm Configuration
SG2
24662
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
78-2
Mode
SG3
24664
Uint32 4
R W n/a
Disabled=0
Enabled=1
78-2
Source
SG3
24666
Uint32 4
R W n/a
Gen=0
Bus 1=1
Bus 2=2
78-2
Pickup
SG3
24668
Float
4
R W Degree
2 - 90
78-2
Alarm Configuration
SG3
24670
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
Battery Voltage
Protection
Weak Battery Mode
GG
24672
Uint32 4
R W n/a
No=0
Yes=1
Battery Voltage
Protection
Undervoltage Mode
GG
24674
Uint32 4
R W n/a
No=0
Yes=1
Battery Voltage
Protection
Overvoltage Mode
GG
24676
Uint32 4
R W n/a
No=0
Yes=1
Battery Voltage
Protection
Weak Battery Threshold
GG
24678
Float
4
R W Volt
4 - 28
Battery Voltage
Protection
Undervoltage Threshold
GG
24680
Float
4
R W Volt
6 - 28
Battery Voltage
Protection
Overvoltage Threshold
GG
24682
Float
4
R W Volt
6 - 32
Battery Voltage
Protection
Weak Battery Time Delay
GG
24684
Float
4
R W Millisecond 0 - 10000
Battery Voltage
Protection
Under Voltage Time Delay
GG
24686
Float
4
R W Millisecond 1000 - 10000
Oil Pressure Protection Alarm Mode
GG
24688
Uint32 4
R W n/a
No=0
Yes=1
Oil Pressure Protection Pre-Alarm Mode
GG
24690
Uint32 4
R W n/a
No=0
Yes=1
Oil Pressure Protection Alarm Threshold
GG
24692
Float
4
R W PSI
2.9 - 150
Oil Pressure Protection Pre-Alarm Threshold
GG
24694
Float
4
R W PSI
2.9 - 150
Oil Pressure Protection Arming Delay
GG
24696
Float
4
R W Millisecond 5000 - 60000
Coolant Temperature
Protection
High Coolant Temp Alarm Mode GG
24698
Uint32 4
R W n/a
No=0
Yes=1
Coolant Temperature
Protection
High Coolant Temp Pre-Alarm
Mode
GG
24700
Uint32 4
R W n/a
No=0
Yes=1
Coolant Temperature
Protection
Low Coolant Temp Pre-Alarm
Mode
GG
24702
Uint32 4
R W n/a
No=0
Yes=1
Coolant Temperature
Protection
High Coolant Temp Alarm
Threshold
GG
24704
Float
4
R W Deg F
100 - 280