Basler Electric DGC-2020HD Modbus Protocol User Manual
Page 71

9469300991 Rev A
65
DGC-2020HD Modbus
™ Protocol
Default Register Table
Name
Description
Group Register
Type
Bytes R/W
Unit
Range
Bus 1 Volt Config
Ratio Secondary
GG
6538
Float
4
R W n/a
1 - 600
Bus 1 Volt Config
Rated Primary LL
GG
6540
Float
4
R W Volt
1 - 500000
Bus 2 Volt Config
Connection
GG
6542
Int32
4
R W n/a
Delta=7
Wye=8
1 Phase AB=0
1 Phase AC=2
Grounded Delta=9
Bus 2 Volt Config
Ratio Primary
GG
6544
Float
4
R W n/a
1 - 500000
Bus 2 Volt Config
Ratio Secondary
GG
6546
Float
4
R W n/a
1 - 600
Bus 2 Volt Config
Rated Primary LL
GG
6548
Float
4
R W Volt
1 - 500000
Gen Current
Configuration
Connection
GG
6550
Int32
4
R W n/a
CT A=0
CT B=1
CT C=2
CT AB=3
CT BC=4
CT CA=5
CT ABC=6
Gen Current
Configuration
Ratio Primary
GG
6552
Float
4
R W n/a
1 - 9999
Gen Current
Configuration
Ratio Secondary
GG
6554
Int32
4
R W n/a
1=1
5=5
Gen Current
Configuration
Rated Primary
GG
6556
Float
4
R
Amp
0 - 180000
Bus 1 Current Config
Connection
GG
6558
Int32
4
R W n/a
CT A=0
CT B=1
CT C=2
CT AB=3
CT BC=4
CT CA=5
CT ABC=6
Bus 1 Current Config
Ratio Primary
GG
6560
Float
4
R W n/a
1 - 9999
Bus 1 Current Config
Ratio Secondary
GG
6562
Int32
4
R W n/a
1=1
5=5
Bus 1 Current Config
Rated Primary
GG
6564
Float
4
R
Amp
0 - 180000
Bus 2 Current Config
Connection
GG
6566
Int32
4
R W n/a
CT A=0
CT B=1
CT C=2
CT AB=3
CT BC=4
CT CA=5
CT ABC=6
Bus 2 Current Config
Ratio Primary
GG
6568
Float
4
R W n/a
1 - 9999
Bus 2 Current Config
Ratio Secondary
GG
6570
Int32
4
R W n/a
1=1
5=5
Bus 2 Current Config
Rated Primary
GG
6572
Float
4
R
Amp
0 - 180000
Gen Config
Rated PF
GG
6574
Float
4
R W Power
Factor
-2 - 2
Gen Config
Rated kW
GG
6576
Float
4
R W kilowatt 0 - 1000000
Gen Config
Rotation
GG
6578
Int32
4
R W n/a
ABC=0
ACB=1
Bus 1 Config
Rated PF
GG
6580-81 Float
4
R W Power
Factor
-2 - 2
Bus 1 Config
Rated kW
GG
6582
Float
4
R W kilowatt 0 - 1000000
Reserved
6584
Bus 2 Config
Rated PF
GG
6586-87 Float
4
R W Power
Factor
-2 - 2
Bus 2 Config
Rated kW
GG
6588
Float
4
R W kilowatt 0 - 1000000
Reserved
6590
RS232 Settings
Baud Rate
GG
6592
Uint32
4
R W n/a
1200 Baud=1200
2400 Baud=2400
4800 Baud=4800
9600 Baud=9600
19200 Baud=19200
38400 Baud=38400
57600 Baud=57600
115200 Baud=115200
RS232 Settings
Parity
GG
6594
Uint32
4
R W n/a
Even Parity=0
Odd Parity=1
No Parity=2
RS232 Settings
Bits Per Character
GG
6596
Uint32
4
R W n/a
8-Bits=8
7-Bits=7
RS232 Settings
Stop Bits
GG
6598
Uint32
4
R W n/a
1 Stop Bit=1
2 Stop Bits=2