Basler Electric DGC-2020HD Modbus Protocol User Manual
Page 128
![background image](https://www.manualsdir.com/files/773959/content/doc128.png)
122
9469300991 Rev A
Default Register Table
DGC-2020HD Modbus
™ Protocol
Name
Description
Group Register Type Bytes R/W
Unit
Range
AEM 2 Analog Input 5=322
AEM 2 Analog Input 6=323
AEM 2 Analog Input 7=324
AEM 2 Analog Input 8=325
AEM 2 RTD Input 1=326
AEM 2 RTD Input 2=327
AEM 2 RTD Input 3=328
AEM 2 RTD Input 4=329
AEM 2 RTD Input 5=330
AEM 2 RTD Input 6=331
AEM 2 RTD Input 7=332
AEM 2 RTD Input 8=333
AEM 2 TC Input 1=334
AEM 2 TC Input 2=335
AEM 3 Analog Input 1=336
AEM 3 Analog Input 2=337
AEM 3 Analog Input 3=338
AEM 3 Analog Input 4=339
AEM 3 Analog Input 5=340
AEM 3 Analog Input 6=341
AEM 3 Analog Input 7=342
AEM 3 Analog Input 8=343
AEM 3 RTD Input 1=344
AEM 3 RTD Input 2=345
AEM 3 RTD Input 3=346
AEM 3 RTD Input 4=347
AEM 3 RTD Input 5=348
AEM 3 RTD Input 6=349
AEM 3 RTD Input 7=350
AEM 3 RTD Input 8=351
AEM 3 TC Input 1=352
AEM 3 TC Input 2=353
AEM 4 Analog Input 1=354
AEM 4 Analog Input 2=355
AEM 4 Analog Input 3=356
AEM 4 Analog Input 4=357
AEM 4 Analog Input 5=358
AEM 4 Analog Input 6=359
AEM 4 Analog Input 7=360
AEM 4 Analog Input 8=361
AEM 4 RTD Input 1=362
AEM 4 RTD Input 2=363
AEM 4 RTD Input 3=364
AEM 4 RTD Input 4=365
AEM 4 RTD Input 5=366
AEM 4 RTD Input 6=367
AEM 4 RTD Input 7=368
AEM 4 RTD Input 8=369
AEM 4 TC Input 1=370
AEM 4 TC Input 2=371
AVR Output=372
GOV Output=373
LS Output=374
AEM 4 Remote Analog
Output 4
Out-of-Range Activation
Delay
GG
8616
Float
4
R W Second 0 - 300
AEM 4 Remote Analog
Output 4
Parameter Minimum
GG
8618
Float
4
R W n/a
-999999 - 999999
AEM 4 Remote Analog
Output 4
Parameter Maximum
GG
8620
Float
4
R W n/a
-999999 - 999999
AEM 4 Remote Analog
Output 4
Current Minimum
GG
8622
Float
4
R W Milliamp 4 - 20
AEM 4 Remote Analog
Output 4
Current Maximum
GG
8624
Float
4
R W Milliamp 4 - 20
AEM 4 Remote Analog
Output 4
Voltage Minimum
GG
8626
Float
4
R W Volt
0 - 10
AEM 4 Remote Analog
Output 4
Voltage Maximum
GG
8628
Float
4
R W Volt
0 - 10
AEM 4 Remote Analog
Output 4
Alarm Configuration
GG
8630
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
Analog Input 1 Protection
Parameter Minimum
GG
8632
Float
4
R W n/a
-999999 - 999999
Analog Input 1 Protection
Parameter Maximum
GG
8634
Float
4
R W n/a
-999999 - 999999
Analog Input 1 Protection
Current Minimum
GG
8636
Float
4
R W Milliamp 4 - 20
Analog Input 1 Protection
Current Maximum
GG
8638
Float
4
R W Milliamp 4 - 20
Analog Input 1 Protection
Voltage Minimum
GG
8640
Float
4
R W Volt
0 - 10
Analog Input 1 Protection
Voltage Maximum
GG
8642
Float
4
R W Volt
0 - 10
Analog Input 1 Protection
Alarm Configuration
GG
8644
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
Analog Input 1 Protection
Hysteresis
GG
8646
Float
4
R W Percent 0 - 100
Analog Input 1 Protection
Arming Delay
GG
8648
Float
4
R W Second 0 - 300