Default Register Table

DGC-2020HD Modbus

™ Protocol

Name

Description

Group Register Type Bytes R/W

Unit

Range

51-4

Constant A

SG2 3P 23938

Float

4

R W n/a

0 - 600

51-4

Constant B

SG2 3P 23940

Float

4

R W n/a

0 - 25

51-4

Constant C

SG2 3P 23942

Float

4

R W n/a

0 - 1

51-4

Constant N

SG2 3P 23944

Float

4

R W n/a

0.5 - 2.5

51-4

Constant R

SG2 3P 23946

Float

4

R W n/a

0 - 30

51-4

Voltage Restraint Setpoint

SG2 3P 23948

Float

4

R W Volt

30 - 250

51-4

Voltage Restraint Mode

SG2 3P 23950

Uint32 4

R W n/a

Disabled=0
Control=1

Restraint=2

51-4

Alarm Configuration

SG2 3P 23952

Uint32 4

R W n/a

Status Only=0

Pre-Alarm=1
Alarm=2

51-4

Low-Line Scale

SG2 3P 23954

Float

4

R W n/a

0.001 - 3

51-4

Voltage Restraint Source

SG2 3P 23956

Uint32 4

R W n/a

Gen=0

Bus 1=1
Bus 2=2

51-4

Constant Q

SG2 3P 23958

Float

4

R W n/a

0.1 - 10

51-4

Mode

SG3 1P 23960

Uint32 4

R W n/a

Disabled=0
IA=1

IB=2
IC=3

Imax=4

3I0=5
I2=6

IG=7
I1=8

51-4

Source

SG3 1P 23962

Uint32 4

R W n/a

Gen=0
Bus 1=1

Bus 2=2

51-4

Pickup

SG3 1P 23964

Float

4

R W Amp

0.9 - 7.75

51-4

Curve Index

SG3 1P 23966

Uint32 4

R W n/a

S1=0

S2=1

L1=2
L2=3

D=4
M=5

I1=6
I2=7

V1=8

V2=9
E1=10

E2=11
A=12

B=13
C=14

G=15
F=16

46=17

P=18

51-4

Direction

SG3 1P 23968

Uint32 4

R W n/a

Forward=0
Reverse=1

Non-Directional=2

51-4

Use Instantaneous Reset

SG3 1P 23970

Uint32 4

R W n/a

Integrating=0

Instantaneous=1

51-4

Constant TD

SG3 1P 23972

Float

4

R W n/a

0 - 9.9

51-4

Constant A

SG3 1P 23974

Float

4

R W n/a

0 - 600

51-4

Constant B

SG3 1P 23976

Float

4

R W n/a

0 - 25

51-4

Constant C

SG3 1P 23978

Float

4

R W n/a

0 - 1

51-4

Constant N

SG3 1P 23980

Float

4

R W n/a

0.5 - 2.5

51-4

Constant R

SG3 1P 23982

Float

4

R W n/a

0 - 30

51-4

Voltage Restraint Setpoint

SG3 1P 23984

Float

4

R W Volt

30 - 250

51-4

Voltage Restraint Mode

SG3 1P 23986

Uint32 4

R W n/a

Disabled=0

Control=1

Restraint=2

51-4

Alarm Configuration

SG3 1P 23988

Uint32 4

R W n/a

Status Only=0
Pre-Alarm=1

Alarm=2

51-4

Low-Line Scale

SG3 1P 23990

Float

4

R W n/a

0.001 - 3

51-4

Voltage Restraint Source

SG3 1P 23992

Uint32 4

R W n/a

Gen=0
Bus 1=1

Bus 2=2

51-4

Constant Q

SG3 1P 23994

Float

4

R W n/a

0.1 - 10