DGC-2020HD Modbus

™ Protocol

Default Register Table

Name

Description

Group Register Type Bytes R/W

Unit

Range

51-2

Mode

SG3 3P 23420

Uint32 4

R W n/a

Disabled=0
IA=1

IB=2

IC=3
Imax=4

3I0=5
I2=6

IG=7
I1=8

51-2

Source

SG3 3P 23422

Uint32 4

R W n/a

Gen=0
Bus 1=1

Bus 2=2

51-2

Pickup

SG3 3P 23424

Float

4

R W Amp

0.9 - 7.75

51-2

Curve Index

SG3 3P 23426

Uint32 4

R W n/a

S1=0
S2=1

L1=2
L2=3

D=4
M=5

I1=6
I2=7

V1=8

V2=9
E1=10

E2=11
A=12

B=13
C=14

G=15

F=16
46=17

P=18

51-2

Direction

SG3 3P 23428

Uint32 4

R W n/a

Forward=0

Reverse=1
Non-Directional=2

51-2

Use Instantaneous Reset

SG3 3P 23430

Uint32 4

R W n/a

Integrating=0

Instantaneous=1

51-2

Constant TD

SG3 3P 23432

Float

4

R W n/a

0 - 9.9

51-2

Constant A

SG3 3P 23434

Float

4

R W n/a

0 - 600

51-2

Constant B

SG3 3P 23436

Float

4

R W n/a

0 - 25

51-2

Constant C

SG3 3P 23438

Float

4

R W n/a

0 - 1

51-2

Constant N

SG3 3P 23440

Float

4

R W n/a

0.5 - 2.5

51-2

Constant R

SG3 3P 23442

Float

4

R W n/a

0 - 30

51-2

Voltage Restraint Setpoint

SG3 3P 23444

Float

4

R W Volt

30 - 250

51-2

Voltage Restraint Mode

SG3 3P 23446

Uint32 4

R W n/a

Disabled=0
Control=1

Restraint=2

51-2

Alarm Configuration

SG3 3P 23448

Uint32 4

R W n/a

Status Only=0

Pre-Alarm=1
Alarm=2

51-2

Low-Line Scale

SG3 3P 23450

Float

4

R W n/a

0.001 - 3

51-2

Voltage Restraint Source

SG3 3P 23452

Uint32 4

R W n/a

Gen=0
Bus 1=1

Bus 2=2

51-2

Constant Q

SG3 3P 23454

Float

4

R W n/a

0.1 - 10

51-3

Mode

SG0 1P 23456

Uint32 4

R W n/a

Disabled=0
IA=1

IB=2
IC=3

Imax=4
3I0=5

I2=6

IG=7
I1=8

51-3

Source

SG0 1P 23458

Uint32 4

R W n/a

Gen=0

Bus 1=1

Bus 2=2

51-3

Pickup

SG0 1P 23460

Float

4

R W Amp

0.9 - 7.75