Basler Electric DGC-2020HD Modbus Protocol User Manual
Page 297

9469300991 Rev A
291
DGC-2020HD Modbus
™ Protocol
Legacy Register Table
Register
Description
Type
Units
Scaling
Factor
R/W
Range
46424
AEM Input 4 Max Voltage
Int32
DeciVolt
Deci
RW 0 - 100
46426
AEM Input 4 Max Current
Int32
Milliamp x
10
Deci
RW 40 - 200
46428
AEM Input 4 Min Voltage
Int32
DeciVolt
Deci
RW 0 - 100
46430
AEM Input 4 Min Current
Int32
Milliamp x
10
Deci
RW 40 - 200
46432
AEM Input 4 Param Max
Int32
Centi Unit
Centi
RW (-100000000) – 99999900
46434
AEM Input 4 Param Min
Int32
Centi Unit
Centi
RW (-100000000) – 99999900
46436
AEM Input 4 Hysteresis
Int32
Deci
Percent
Deci
RW 0 – 1000
46438
AEM Input 4 Arming Delay
Int32
Second
n/a
RW 0 – 300
46440
AEM Input 4 Threshold 1 Activation Delay
Int32
Second
n/a
RW 0 – 300
46442
AEM Input 4 Threshold 2 Activation Delay
Int32
Second
n/a
RW 0 – 300
46444
AEM Input 4 Over 1 Threshold
Int32
Centi Unit
Centi
RW (-100000000) – 99999900
46446
AEM Input 4 Over 2 Threshold
Int32
Centi Unit
Centi
RW (-100000000) – 99999900
46448
AEM Input 4 Under 1 Threshold
Int32
Centi Unit
Centi
RW (-100000000) – 99999900
46450
AEM Input 4 Under 2 Threshold
Int32
Centi Unit
Centi
RW (-100000000) – 99999900
46452
AEM Input 4 Over 1 Alarm Type
Int32
n/a
n/a
RW 0 = Status Only
1 = Pre-Alarm
2 = Alarm
46454
AEM Input 4 Over 2 Alarm Type
Int32
n/a
n/a
RW 0 = Status Only
1 = Pre-Alarm
2 = Alarm
46456
AEM Input 4 Under 1 Alarm Type
Int32
n/a
n/a
RW 0 = Status Only
1 = Pre-Alarm
2 = Alarm
46458
AEM Input 4 Under 2 Alarm Type
Int32
n/a
n/a
RW 0 = Status Only
1 = Pre-Alarm
2 = Alarm
46460
AEM Input 4 Out of Range Alarm Type
Int32
n/a
n/a
RW 0 = Status Only
1 = Pre-Alarm
2 = Alarm
46462 -
46498
Reserved
46500
AEM Input 5 Max Voltage
Int32
DeciVolt
Deci
RW 0 - 100
46502
AEM Input 5 Max Current
Int32
Milliamp x
10
Deci
RW 40 - 200
46504
AEM Input 5 Min Voltage
Int32
DeciVolt
Deci
RW 0 - 100
46506
AEM Input 5 Min Current
Int32
Milliamp x
10
Deci
RW 40 - 200
46508
AEM Input 5 Param Max
Int32
Centi Unit
Centi
RW (-100000000) – 99999900
46510
AEM Input 5 Param Min
Int32
Centi Unit
Centi
RW (-100000000) – 99999900
46512
AEM Input 5 Hysteresis
Int32
Deci
Percent
Deci
RW 0 – 1000
46514
AEM Input 5 Arming Delay
Int32
Second
n/a
RW 0 – 300
46516
AEM Input 5 Threshold 1 Activation Delay
Int32
Second
n/a
RW 0 – 300
46518
AEM Input 5 Threshold 2 Activation Delay
Int32
Second
n/a
RW 0 – 300
46520
AEM Input 5 Over 1 Threshold
Int32
Centi Unit
Centi
RW (-100000000) – 99999900
46522
AEM Input 5 Over 2 Threshold
Int32
Centi Unit
Centi
RW (-100000000) – 99999900
46524
AEM Input 5 Under 1 Threshold
Int32
Centi Unit
Centi
RW (-100000000) – 99999900
46526
AEM Input 5 Under 2 Threshold
Int32
Centi Unit
Centi
RW (-100000000) – 99999900
46528
AEM Input 5 Over 1 Alarm Type
Int32
n/a
n/a
RW 0 = Status Only
1 = Pre-Alarm
2 = Alarm
46530
AEM Input 5 Over 2 Alarm Type
Int32
n/a
n/a
RW 0 = Status Only
1 = Pre-Alarm
2 = Alarm
46532
AEM Input 5 Under 1 Alarm Type
Int32
n/a
n/a
RW 0 = Status Only
1 = Pre-Alarm
2 = Alarm
46534
AEM Input 5 Under 2 Alarm Type
Int32
n/a
n/a
RW 0 = Status Only
1 = Pre-Alarm
2 = Alarm
46536
AEM Input 5 Out of Range Alarm Type
Int32
n/a
n/a
RW 0 = Status Only
1 = Pre-Alarm
2 = Alarm
46538
AEM Input 6 Max Voltage
Int32
DeciVolt
Deci
RW 0 - 100
46540
AEM Input 6 Max Current
Int32
Milliamp x
10
Deci
RW 40 - 200
46542
AEM Input 6 Min Voltage
Int32
DeciVolt
Deci
RW 0 - 100
46544
AEM Input 6 Min Current
Int32
Milliamp x
10
Deci
RW 40 - 200
46546
AEM Input 6 Param Max
Int32
Centi Unit
Centi
RW (-100000000) – 99999900
46548
AEM Input 6 Param Min
Int32
Centi Unit
Centi
RW (-100000000) – 99999900
46550
AEM Input 6 Hysteresis
Int32
Deci
Percent
Deci
RW 0 – 1000
46552
AEM Input 6 Arming Delay
Int32
Second
n/a
RW 0 – 300
46554
AEM Input 6 Threshold 1 Activation Delay
Int32
Second
n/a
RW 0 – 300