Basler Electric DGC-2020HD Modbus Protocol User Manual
Page 147
9469300991 Rev A
141
DGC-2020HD Modbus
™ Protocol
Default Register Table
Name
Description
Group Register Type Bytes R/W
Unit
Range
27P-6
Time Delay
SG3 3P 20664
Float
4
R W Millisecond 0 - 600000
27P-6
Alarm Configuration
SG3 3P 20666
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
27P-6
Low-Line Scale
SG3 3P 20668
Float
4
R W n/a
0.001 - 3
27P-6
Frequency Inhibit
SG3 3P 20670
Float
4
R W Hertz
20 - 90
59P-1
Mode
SG0 1P 20672
Uint32 4
R W n/a
Disabled=0
Enabled=1
59P-1
Source
SG0 1P 20674
Uint32 4
R W n/a
Gen=0
Bus 1=1
Bus 2=2
59P-1
Pickup
SG0 1P 20676
Float
4
R W Volt
1 - 576
59P-1
Time Delay
SG0 1P 20678
Float
4
R W Millisecond 0 - 600000
59P-1
Alarm Configuration
SG0 1P 20680
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
59P-1
Low-Line Scale
SG0 1P 20682
Float
4
R W n/a
0.001 - 3
59P-1
Mode
SG0 3P 20684
Uint32 4
R W n/a
Disabled=0
Enabled=1
59P-1
Source
SG0 3P 20686
Uint32 4
R W n/a
Gen=0
Bus 1=1
Bus 2=2
59P-1
Pickup
SG0 3P 20688
Float
4
R W Volt
1 - 576
59P-1
Time Delay
SG0 3P 20690
Float
4
R W Millisecond 0 - 600000
59P-1
Alarm Configuration
SG0 3P 20692
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
59P-1
Low-Line Scale
SG0 3P 20694
Float
4
R W n/a
0.001 - 3
59P-1
Mode
SG1 1P 20696
Uint32 4
R W n/a
Disabled=0
Enabled=1
59P-1
Source
SG1 1P 20698
Uint32 4
R W n/a
Gen=0
Bus 1=1
Bus 2=2
59P-1
Pickup
SG1 1P 20700
Float
4
R W Volt
1 - 576
59P-1
Time Delay
SG1 1P 20702
Float
4
R W Millisecond 0 - 600000
59P-1
Alarm Configuration
SG1 1P 20704
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
59P-1
Low-Line Scale
SG1 1P 20706
Float
4
R W n/a
0.001 - 3
59P-1
Mode
SG1 3P 20708
Uint32 4
R W n/a
Disabled=0
Enabled=1
59P-1
Source
SG1 3P 20710
Uint32 4
R W n/a
Gen=0
Bus 1=1
Bus 2=2
59P-1
Pickup
SG1 3P 20712
Float
4
R W Volt
1 - 576
59P-1
Time Delay
SG1 3P 20714
Float
4
R W Millisecond 0 - 600000
59P-1
Alarm Configuration
SG1 3P 20716
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
59P-1
Low-Line Scale
SG1 3P 20718
Float
4
R W n/a
0.001 - 3
59P-1
Mode
SG2 1P 20720
Uint32 4
R W n/a
Disabled=0
Enabled=1
59P-1
Source
SG2 1P 20722
Uint32 4
R W n/a
Gen=0
Bus 1=1
Bus 2=2
59P-1
Pickup
SG2 1P 20724
Float
4
R W Volt
1 - 576
59P-1
Time Delay
SG2 1P 20726
Float
4
R W Millisecond 0 - 600000
59P-1
Alarm Configuration
SG2 1P 20728
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
59P-1
Low-Line Scale
SG2 1P 20730
Float
4
R W n/a
0.001 - 3
59P-1
Mode
SG2 3P 20732
Uint32 4
R W n/a
Disabled=0
Enabled=1
59P-1
Source
SG2 3P 20734
Uint32 4
R W n/a
Gen=0
Bus 1=1
Bus 2=2
59P-1
Pickup
SG2 3P 20736
Float
4
R W Volt
1 - 576
59P-1
Time Delay
SG2 3P 20738
Float
4
R W Millisecond 0 - 600000
59P-1
Alarm Configuration
SG2 3P 20740
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
59P-1
Low-Line Scale
SG2 3P 20742
Float
4
R W n/a
0.001 - 3
59P-1
Mode
SG3 1P 20744
Uint32 4
R W n/a
Disabled=0
Enabled=1
59P-1
Source
SG3 1P 20746
Uint32 4
R W n/a
Gen=0
Bus 1=1
Bus 2=2
59P-1
Pickup
SG3 1P 20748
Float
4
R W Volt
1 - 576