Basler Electric DGC-2020HD Modbus Protocol User Manual
Page 153

9469300991 Rev A
147
DGC-2020HD Modbus
™ Protocol
Default Register Table
Name
Description
Group Register Type Bytes R/W
Unit
Range
59P-6
Alarm Configuration
SG0 3P 21172
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
59P-6
Low-Line Scale
SG0 3P 21174
Float
4
R W n/a
0.001 - 3
59P-6
Mode
SG1 1P 21176
Uint32 4
R W n/a
Disabled=0
Enabled=1
59P-6
Source
SG1 1P 21178
Uint32 4
R W n/a
Gen=0
Bus 1=1
Bus 2=2
59P-6
Pickup
SG1 1P 21180
Float
4
R W Volt
1 - 576
59P-6
Time Delay
SG1 1P 21182
Float
4
R W Millisecond 0 - 600000
59P-6
Alarm Configuration
SG1 1P 21184
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
59P-6
Low-Line Scale
SG1 1P 21186
Float
4
R W n/a
0.001 - 3
59P-6
Mode
SG1 3P 21188
Uint32 4
R W n/a
Disabled=0
Enabled=1
59P-6
Source
SG1 3P 21190
Uint32 4
R W n/a
Gen=0
Bus 1=1
Bus 2=2
59P-6
Pickup
SG1 3P 21192
Float
4
R W Volt
1 - 576
59P-6
Time Delay
SG1 3P 21194
Float
4
R W Millisecond 0 - 600000
59P-6
Alarm Configuration
SG1 3P 21196
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
59P-6
Low-Line Scale
SG1 3P 21198
Float
4
R W n/a
0.001 - 3
59P-6
Mode
SG2 1P 21200
Uint32 4
R W n/a
Disabled=0
Enabled=1
59P-6
Source
SG2 1P 21202
Uint32 4
R W n/a
Gen=0
Bus 1=1
Bus 2=2
59P-6
Pickup
SG2 1P 21204
Float
4
R W Volt
1 - 576
59P-6
Time Delay
SG2 1P 21206
Float
4
R W Millisecond 0 - 600000
59P-6
Alarm Configuration
SG2 1P 21208
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
59P-6
Low-Line Scale
SG2 1P 21210
Float
4
R W n/a
0.001 - 3
59P-6
Mode
SG2 3P 21212
Uint32 4
R W n/a
Disabled=0
Enabled=1
59P-6
Source
SG2 3P 21214
Uint32 4
R W n/a
Gen=0
Bus 1=1
Bus 2=2
59P-6
Pickup
SG2 3P 21216
Float
4
R W Volt
1 - 576
59P-6
Time Delay
SG2 3P 21218
Float
4
R W Millisecond 0 - 600000
59P-6
Alarm Configuration
SG2 3P 21220
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
59P-6
Low-Line Scale
SG2 3P 21222
Float
4
R W n/a
0.001 - 3
59P-6
Mode
SG3 1P 21224
Uint32 4
R W n/a
Disabled=0
Enabled=1
59P-6
Source
SG3 1P 21226
Uint32 4
R W n/a
Gen=0
Bus 1=1
Bus 2=2
59P-6
Pickup
SG3 1P 21228
Float
4
R W Volt
1 - 576
59P-6
Time Delay
SG3 1P 21230
Float
4
R W Millisecond 0 - 600000
59P-6
Alarm Configuration
SG3 1P 21232
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
59P-6
Low-Line Scale
SG3 1P 21234
Float
4
R W n/a
0.001 - 3
59P-6
Mode
SG3 3P 21236
Uint32 4
R W n/a
Disabled=0
Enabled=1
59P-6
Source
SG3 3P 21238
Uint32 4
R W n/a
Gen=0
Bus 1=1
Bus 2=2
59P-6
Pickup
SG3 3P 21240
Float
4
R W Volt
1 - 576
59P-6
Time Delay
SG3 3P 21242
Float
4
R W Millisecond 0 - 600000
59P-6
Alarm Configuration
SG3 3P 21244
Uint32 4
R W n/a
Status Only=0
Pre-Alarm=1
Alarm=2
59P-6
Low-Line Scale
SG3 3P 21246
Float
4
R W n/a
0.001 - 3
47-1
Mode
SG0
21248
Uint32 4
R W n/a
Disabled=0
V2=3
47-1
Source
SG0
21250
Uint32 4
R W n/a
Gen=0
Bus 1=1
Bus 2=2
47-1
Pickup
SG0
21252
Float
4
R W Volt
1 - 150
47-1
Time Delay
SG0
21254
Float
4
R W Millisecond 0 - 600000