beautypg.com

Bias control – Basler Electric DGC-2020HD Modbus Protocol User Manual

Page 56

background image

50

9469300991 Rev A

Default Register Table

DGC-2020HD Modbus

™ Protocol

Name

Description

Register Bit Type Bytes R/W

Range

GOV Output

Out-of-Range Pre-Alarm

1134

7

Uint16 2

R

False=0 True=1

GOV Output

Out-of-Range Alarm

1134

8

Uint16 2

R

False=0 True=1

LS Output

Out-of-Range

1134

9

Uint16 2

R

False=0 True=1

LS Output

Out-of-Range Pre-Alarm

1134

10 Uint16 2

R

False=0 True=1

LS Output

Out-of-Range Alarm

1134

11 Uint16 2

R

False=0 True=1

Bias Control

Name

Description

Group

Register

Type

Bytes R/W

Unit

Range

Bias Control

AVR Kp For Analog Bias Out

GG

2000

Float

4

R W n/a

0 - 1000

Bias Control

AVR Ki For Analog Bias Out

GG

2002

Float

4

R W n/a

0 - 1000

Bias Control

AVR Kd For Analog Bias Out

GG

2004

Float

4

R W n/a

0 - 1000

Bias Control

AVR Td

GG

2006

Float

4

R W n/a

0 - 1

Bias Control

AVR Loop Gain For Analog Bias Out

GG

2008

Float

4

R W n/a

0 - 1000

Bias Control

AVR Enable Windup Limit

GG

2010

Uint32

4

R W n/a

Disabled=0
Enabled=1

Bias Control

AVR Integrator Limit Plus

GG

2012

Float

4

R W n/a

0 - 1000

Bias Control

AVR Integrator Limit Minus

GG

2014

Float

4

R W n/a

-1000 - 0

Bias Control

AVR Output Upper Limit

GG

2016

Float

4

R W n/a

0 - 1000

Bias Control

AVR Output Lower Limit

GG

2018

Float

4

R W n/a

-1000 - 0

Bias Control

GOV Kp For Analog Bias Out

GG

2020

Float

4

R W n/a

0 - 1000

Bias Control

GOV Ki For Analog Bias Out

GG

2022

Float

4

R W n/a

0 - 1000

Bias Control

GOV Kd For Analog Bias Out

GG

2024

Float

4

R W n/a

0 - 1000

Bias Control

GOV Td

GG

2026

Float

4

R W n/a

0 - 1

Bias Control

GOV Loop Gain For Analog Bias Out

GG

2028

Float

4

R W n/a

0 - 1000

Bias Control

GOV Enable Windup Limit

GG

2030

Uint32

4

R W n/a

Disabled=0
Enabled=1

Bias Control

GOV Integrator Limit Plus

GG

2032

Float

4

R W n/a

0 - 1000

Bias Control

GOV Integrator Limit Minus

GG

2034

Float

4

R W n/a

-1000 - 0

Bias Control

GOV Output Upper Limit

GG

2036

Float

4

R W n/a

0 - 1000

Bias Control

GOV Output Lower Limit

GG

2038

Float

4

R W n/a

-1000 - 0

Bias Control

kvar Kp For Analog Bias Out

GG

2040

Float

4

R W n/a

0 - 1000

Bias Control

kvar Ki For Analog Bias Out

GG

2042

Float

4

R W n/a

0 - 1000

Bias Control

kvar Kd For Analog Bias Out

GG

2044

Float

4

R W n/a

0 - 1000

Bias Control

kvar Td

GG

2046

Float

4

R W n/a

0 - 1

Bias Control

kvar Loop Gain For Analog Bias Out

GG

2048

Float

4

R W n/a

0 - 1000

Bias Control

kvar Enable Windup Limit

GG

2050

Uint32

4

R W n/a

Disabled=0

Enabled=1

Bias Control

kvar Integrator Limit Plus

GG

2052

Float

4

R W n/a

0 - 1000

Bias Control

kvar Integrator Limit Minus

GG

2054

Float

4

R W n/a

-1000 - 0

Bias Control

kvar Output Upper Limit

GG

2056

Float

4

R W n/a

0 - 1000

Bias Control

kvar Output Lower Limit

GG

2058

Float

4

R W n/a

-1000 - 0

Bias Control

kW Kp For Analog Bias Out

GG

2060

Float

4

R W n/a

0 - 1000

Bias Control

kW Ki For Analog Bias Out

GG

2062

Float

4

R W n/a

0 - 1000

Bias Control

kW Kd For Analog Bias Out

GG

2064

Float

4

R W n/a

0 - 1000

Bias Control

kW Td

GG

2066

Float

4

R W n/a

0 - 1

Bias Control

kW Loop Gain For Analog Bias Out

GG

2068

Float

4

R W n/a

0 - 1000

Bias Control

kW Enable Windup Limit

GG

2070

Uint32

4

R W n/a

Disabled=0

Enabled=1

Bias Control

kW Integrator Limit Plus

GG

2072

Float

4

R W n/a

0 - 1000

Bias Control

kW Integrator Limit Minus

GG

2074

Float

4

R W n/a

-1000 - 0

Bias Control

kW Output Upper Limit

GG

2076

Float

4

R W n/a

0 - 1000

Bias Control

kW Output Lower Limit

GG

2078

Float

4

R W n/a

-1000 - 0

Bias Control

kW Droop Percentage

GG

2080

Float

4

R W Percent

0.5 - 10

Bias Control

Load Control Enabled

GG

2082

Uint32

4

R W n/a

Disabled=0

Enabled=1

Bias Control

kW Load Rate

GG

2084

Float

4

R W Percent

0 - 100

Bias Control

Breaker Open Setpoint

GG

2086

Float

4

R W Percent

0 - 100

Bias Control

AVR Output Type

GG

2088

Uint32

4

R W n/a

Contact=0

Analog=1

Bias Control

GOV Output Type

GG

2090

Uint32

4

R W n/a

Contact=0
Analog=1

Bias Control

Governor Droop Gain

GG

2092

Float

4

R W n/a

0 - 1000

Bias Control

AVR Droop Gain

GG

2094

Float

4

R W n/a

0 - 1000

Bias Control

Speed Trim Enabled

GG

2096

Uint32

4

R W n/a

Disabled=0

Enabled=1

Bias Control

Voltage Trim Enabled

GG

2098

Uint32

4

R W n/a

Disabled=0

Enabled=1

Bias Control

Ramped Watt Demand Per Unit

GG

2100

Float

4

R W n/a

n/a

Bias Control

Watt Demand Per Unit

GG

2102

Float

4

R W n/a

n/a

Bias Control

Ramped var Demand Per Unit

GG

2104

Float

4

R W n/a

n/a

Bias Control

AVR Inner Controller Output

GG

2106

Float

4

R W n/a

n/a

Bias Control

AVR Outer Controller Output

GG

2108

Float

4

R W n/a

n/a

Bias Control

GOV Inner Controller Output

GG

2110

Float

4

R W n/a

n/a