Basler Electric DGC-2020HD Modbus Protocol User Manual
Page 313

9469300991 Rev A
307
DGC-2020HD Modbus
™ Protocol
Legacy Register Table
Register
Description
Type
Units
Scaling
Factor
R/W
Range
46954
High/Low Line Contact Input
Int32
n/a
n/a
RW -1 = None
0 = Input 1
1 = Input 2
2 = Input 3
3 = Input 4
4 = Input 5
5 = Input 6
6 = Input 7
7 = Input 8
8 = Input 9
9 = Input 10
10 = Input 11
11 = Input 12
12 = Input 13
13 = Input 14
14 = Input 15
15 = Input 16
46956
Hi/Lo Line Time Delay
Int32
Second
n/a
RW 0 – 300
46958
Hi/Lo Line Engine Running Only
Int32
n/a
n/a
RW 0 = Always
1 = While Engine Running Only
46960
Grounded Delta Override Contact Input
Int32
n/a
n/a
RW -1 = None
0 = Input 1
1 = Input 2
2 = Input 3
3 = Input 4
4 = Input 5
5 = Input 6
6 = Input 7
7 = Input 8
8 = Input 9
9 = Input 10
10 = Input 11
11 = Input 12
12 = Input 13
13 = Input 14
14 = Input 15
15 = Input 16
46962
Grounded Delta Override Time Delay
Int32
Second
n/a
RW 0 – 300
46964
Grounded Delta Override Engine Running
Only
Int32
n/a
n/a
RW 0 = Always
1 = While Engine Running Only