Register
Description
Type
Units
Scaling
Factor
R/W
Range
46750
User Config Input 1 Config Type
Int32
n/a
n/a
RW 0 = Status Only
1 = Pre-Alarm
2 = Alarm
46752
User Config Input 1 Time Delay
Int32
Second
n/a
RW 0 – 300
46754
User Config Input 1 Engine Running Only
Int32
n/a
n/a
RW 0 = Always
1 = While Engine Running Only
46756
User Config Input 2 Config Type
Int32
n/a
n/a
RW 0 = Status Only
1 = Pre-Alarm
2 = Alarm
46758
User Config Input 2 Time Delay
Int32
Second
n/a
RW 0 – 300
46760
User Config Input 2 Engine Running Only
Int32
n/a
n/a
RW 0 = Always
1 = While Engine Running Only
46762
User Config Input 3 Config Type
Int32
n/a
n/a
RW 0 = Status Only
1 = Pre-Alarm
2 = Alarm
46764
User Config Input 3 Time Delay
Int32
Second
n/a
RW 0 – 300
46766
User Config Input 3 Engine Running Only
Int32
n/a
n/a
RW 0 = Always
1 = While Engine Running Only
46768
User Config Input 4 Config Type
Int32
n/a
n/a
RW 0 = Status Only
1 = Pre-Alarm
2 = Alarm
46770
User Config Input 4 Time Delay
Int32
Second
n/a
RW 0 – 300
46772
User Config Input 4 Engine Running Only
Int32
n/a
n/a
RW 0 = Always
1 = While Engine Running Only
46774
User Config Input 5 Config Type
Int32
n/a
n/a
RW 0 = Status Only
1 = Pre-Alarm
2 = Alarm
46776
User Config Input 5 Time Delay
Int32
Second
n/a
RW 0 – 300
46778
User Config Input 5 Engine Running Only
Int32
n/a
n/a
RW 0 = Always
1 = While Engine Running Only
46780
User Config Input 6 Config Type
Int32
n/a
n/a
RW 0 = Status Only
1 = Pre-Alarm
2 = Alarm
46782
User Config Input 6 Time Delay
Int32
Second
n/a
RW 0 – 300
46784
User Config Input 6 Engine Running Only
Int32
n/a
n/a
RW 0 = Always
1 = While Engine Running Only
46786
User Config Input 7 Config Type
Int32
n/a
n/a
RW 0 = Status Only
1 = Pre-Alarm
2 = Alarm
46788
User Config Input 7 Time Delay
Int32
Second
n/a
RW 0 – 300
46790
User Config Input 7 Engine Running Only
Int32
n/a
n/a
RW 0 = Always
1 = While Engine Running Only
46792
User Config Input 8 Config Type
Int32
n/a
n/a
RW 0 = Status Only
1 = Pre-Alarm
2 = Alarm
46794
User Config Input 8 Time Delay
Int32
Second
n/a
RW 0 – 300
46796
User Config Input 8 Engine Running Only
Int32
n/a
n/a
RW 0 = Always
1 = While Engine Running Only
46798
User Config Input 9 Config Type
Int32
n/a
n/a
RW 0 = Status Only
1 = Pre-Alarm
2 = Alarm
46800
User Config Input 9 Time Delay
Int32
Second
n/a
RW 0 – 300
46802
User Config Input 9 Engine Running Only
Int32
n/a
n/a
RW 0 = Always
1 = While Engine Running Only
46804
User Config Input 10 Config Type
Int32
n/a
n/a
RW 0 = Status Only
1 = Pre-Alarm
2 = Alarm
46806
User Config Input 10 Time Delay
Int32
Second
n/a
RW 0 – 300
46808
User Config Input 10 Engine Running Only
Int32
n/a
n/a
RW 0 = Always
1 = While Engine Running Only
46810
User Config Input 11 Config Type
Int32
n/a
n/a
RW 0 = Status Only
1 = Pre-Alarm
2 = Alarm
46812
User Config Input 11 Time Delay
Int32
Second
n/a
RW 0 – 300
46814
User Config Input 11 Engine Running Only
Int32
n/a
n/a
RW 0 = Always
1 = While Engine Running Only
46816
User Config Input 12 Config Type
Int32
n/a
n/a
RW 0 = Status Only
1 = Pre-Alarm
2 = Alarm
46818
User Config Input 12 Time Delay
Int32
Second
n/a
RW 0 – 300
46820
User Config Input 12 Engine Running Only
Int32
n/a
n/a
RW 0 = Always
1 = While Engine Running Only
46822
User Config Input 13 Config Type
Int32
n/a
n/a
RW 0 = Status Only
1 = Pre-Alarm
2 = Alarm
46824
User Config Input 13 Time Delay
Int32
Second
n/a
RW 0 – 300
46826
User Config Input 13 Engine Running Only
Int32
n/a
n/a
RW 0 = Always
1 = While Engine Running Only