Basler Electric DGC-2020HD Modbus Protocol User Manual
Page 252
246
9469300991 Rev A
Legacy Register Table
DGC-2020HD Modbus
™ Protocol
Register
Description
Type
Units
Scaling
Factor
R/W
Range
44814-15
Pre-Alarm Metering 1
Int32
n/a
n/a
R
Bit 0 = Not Used
Bit 1 = Not Used
Bit 2 = Not Used
Bit 3 = Not Used
Bit 4 = Global Pre-Alarm
Bit 5 = Fuel Filter 2 Leak
Bit 6 = Fuel Filter 1 Leak
Bit 7 = Engine kW Overload 3
Bit 8 = Engine kW Overload 2
Bit 9 = MPU Fail
Bit 10 = Fuel Leak Detect
Bit 11 = Battery Charger Failure
Bit 12 = Low Coolant Level
Bit 13 = Mains Brkr Fail to Open
Bit 14 = Mains Brkr Fail to Close
Bit 15 = Sync Fail at Mains Brkr
Bit 16 = Gen Brkr Fail to Open
Bit 17 = Gen Brkr Fail to Close
Bit 18 = Sync Fail at Gen Brkr
Bit 19 = High Fuel Level
Bit 20 = Loss of Rem. Mod. Com
Bit 21 = Engine kW Overload
Bit 22 = Diagnostic Trouble Code
Bit 23 = Loss of ECU Comms
Bit 24 = Maintenance Due
Bit 25 = Battery Overvoltage
Bit 26 = Weak Battery
Bit 27 = Low Battery Voltage
Bit 28 = Low Coolant Temp
Bit 29 = Low Fuel Level
Bit 30 = Low Oil Pressure
Bit 31 = Hi Coolant Temp
44816-17
MTU Alarm Metering
Int32
n/a
n/a
R
Bit 0 = Not Used
Bit 1 = Not Used
Bit 2 = Not Used
Bit 3 = Not Used
Bit 4 = Not Used
Bit 5 = Not Used
Bit 6 = Not Used
Bit 7 = Not Used
Bit 8 = Not Used
Bit 9 = Not Used
Bit 10 = Not Used
Bit 11 = Not Used
Bit 12 = Not Used
Bit 13 = Not Used
Bit 14 = Not Used
Bit 15 = Not Used
Bit 16 = Not Used
Bit 17 = Not Used
Bit 18 = Not Used
Bit 19 = Not Used
Bit 20 = Not Used
Bit 21 = Not Used
Bit 22 = Not Used
Bit 23 = High ECU Supply
Bit 24 = Combined Red
Bit 25 = Overspeed
Bit 26 = Low Oil Pressure
Bit 27 = Low Fuel Delivery Press.
Bit 28 = Low Aftercooler Coolant Level
Bit 29 = High Coolant Temp
Bit 30 = High Oil Temp
Bit 31 = High Charge Air Temp