A p p e n d i x A :
K - f ac t o r s
To set up a VAV controller, a K-factor must be entered into the controller.
Typically, this is part of the airflow chart that the manufacturer places on the
VAV unit. If this information is missing and not available from the
manufacturer, use the K-factor in the following chart.
Duct size in inches
K-factor
4
265
5
357
6
460
7
652
8
890
9
1145
10
1143
12
1972
14
2771
16
3741
20
2106
22
2106
26
2498
40
7176
24 x 16
6980
Table A–1
Start point K factors
SimplyVAV
Appendix A: K-factors