Cnfg comm blnc pri – KMC Controls BAC-8007 Installation Guide User Manual
Page 44

Procedure
Steps
STE display
1
Starting display
1.
Start at the temperature display.
2.
Press the
and
buttons together.
l
If Password 2 is not required, the display
changes to
CNFG
.
l
If required, enter Password 2. The display
changes to
CNFG
when Password 2 is
correct.
3
237
////
2
Select the
CNFG
display.
1.
From the
CNFG
display, press the
or
buttons to advance to
COMM
and the
BLNC
display.
2.
Press the
Set
Point
button to select
BLNC
. The display
advances to
PRI
.
3.
Press the
Set
Point
button to select
PRI
.
CNFG
COMM
BLNC
PRI
Table 5–1
The airflow balancing procedure
Section 5: Balancing airflow
SimplyVAV
44
Revision E
This manual is related to the following products: