SAE-1101/1102/1151/1152 Carbon Monoxide (CO) Detectors

1

Installation Guide

Installation Guide

Carbon Monoxide (CO) Detectors

SAE-1101/1102/1151/1152

SAE-1101/1102 Space Mount

Install the unit at least five feet above the finished floor

of the area to be controlled. Do not install near doors,

windows, supply air diffusers of other known air

disturbances.

Avoid areas prone to vibration or rapid

temperature change.
1. Remove the cover by loosening and removing the

four screws.

2. Remove a knockout from the top or bottom for

wiring.

3. Attach the universal backplate directly to a

standard electrical box using two screws.

4. After wiring, configuring, and testing the unit,

reinstall the cover.

SAE-1151/1152 Duct Mount

Choose a mounting location in a straight section of

a return air duct. Mount at least 5 feet (or 7.5 duct

diameters) from corners and other items that may

cause disturbances in the air flow. Avoid areas prone

to vibration or rapid temperature change.
1. Cut a 1

1

8

-inch hole in the duct for the air sampling

tube.

2. Remove the cover by loosening and removing the

four screws.

3. Remove a knockout from the top or bottom for

wiring.

4 . Insert the sampling tube into the duct. Use the

foam plug (included) to prevent air from entering

the enclosure, causing false readings.

5. Centering the sensor over the hole in the

ductwork, attach the unit to the ductwork by

threading four screws through the self-sealing

rubber gaskets on the backplate of the housing.

6. After wiring, configuring, and testing the unit,

reinstall the cover.

Mounting

Accessories

IEI-1001

LCD Display Module

(required for configu-

ration)

XEE-6111-040

Transformer, 120-

to-24 VAC, 40 VA,

single-hub

XEE-6112-040

Transformer, 120-to-

24 VAC, 40 VA, dual-

hub

4.9" W (124 mm)

7.22" H

(183 mm)

1.69" D (43 mm)

or

9.9" D (250 mm)

with duct

insertion tube

Models

SAE-1101

Space CO sensor (after 5/2007)

SAE-1102

Space CO sensor with two relays

and audible alarm (after 2/2007)

SAE-1151

Duct CO sensor (after 12/2006)

SAE-1152

Duct CO sensor with two relays

and audible alarm (after 11/2004)

NOTE: These instructions apply to units

manufactured after the corresponding

dates shown in the Models list. For older

units (with a row of LEDs on the left side

of the board), see the original version of

this installation guide available on www.

kmccontrols.com.