beautypg.com

KMC Controls STE-1414 User Manual

Installation guide, Duct temperature sensor, averaging (copper tubing), Mounting

background image

STE-1411/1412/1413/1414

1

Installation Guide

Installation Guide

Duct Temperature Sensor, Averaging (Copper Tubing)

STE-1411/1412/1413/1414

Mounting

The averaging temperature sensor incorporates sev-

eral discrete sensors encapsulated at equal distances

across the length of the copper tubing probe. The

complete assembly acts as a single sensor to moni-

tor the average temperature in a duct. Averaging

elements are not recommended for high humidity

applications.
The copper tubing can be installed onto hangers in

the duct using tube clamps or wire ties. It should

be located in a straight section of duct away from

heating, cooling, or humidifier elements.

Mounting 1
Connections and Wiring 2
Configuration 2
Maintenance 2
Specifications 2
More Information 2
Important Notices 2

Temperature sensors can be affected by air stratifica-

tion in the duct, air leakage through the conduit

or other duct holes, and nearness to exterior walls,

a large thermal mass (e.g., concrete blocks), heat

sources, or wires with power.
Because of air stratification, the coldest air tends to

be toward the bottom of the duct. Hence, one of the

sensors inside the tubing should be near the bottom

of the duct.
1. Cut a hole in the duct large enough to feed the

copper probe through the back of the sensor

enclosure.

2. Fasten the enclosure to the duct by drilling holes

in the duct and threading screws through the

mounting holes in the case.

3. Insert the sensor probe into the duct, bend the

probe tubing to cover the air path, and secure

as needed. Maintain a minimum bend radius

of six inches to prevent damage to the wires or

sensors.

4. For the cable leading to the building automation

system controller, attach conduit to a hole in one

of the sides.

Use

Tie Wraps

to Secure

Tubing

6"

Min.

Bend

Radius

7.94 mm

0.3125"

Soft Copper Probe

115.8 mm

4.56"

Foam Gasket

53.6 mm

2.110"

2X Ø 0.850"

(Standard)

Plastic Enclosure

107.7 mm

4.24"

Various

Probe

Lengths

Various

Probe

Lengths

8X Ø 0.875"

84.3 mm

3.452"

53.3 mm

2.10"

51.8 mm

2.04"

101.6 mm

4.0"

Metal Enclosure (M)

98.4 mm

3.875"

7.94 mm

0.3125"

Soft Copper Probe

84.3 mm

3.320"

Mounting Holes (X2) Ш 0.200"