Pri sec, Smax – KMC Controls BAC-8007 Installation Guide User Manual

Page 46

background image

Procedure

Steps

STE display

5

Advance or exit

1.

Press the or buttons to select one of the
following:

SEC

to balance the secondary VAV for dual

duct systems. Choosing

SEC

advances to

the

SMAX

display. This is available only on

dual duct models.

BACK

to choose another commissioning

function

EXIT

to return to the temperature display.

2.

Press the

Set

Point

button to select the next function.

PRI

SEC

6

Measure and enter the
actual maximum
secondary airflow

The display begins flashing

SMAX

and also

displays the actual airflow at the bottom.

Note:

The airflow displayed by the STE-8000

in this step is the actual, uncorrected airflow.

1.

Wait for the maximum airflow value to
stabilize.

2.

With a flow hood, measure the actual airflow.

3.

Press the

Set

Point

button to advance to the entry

display.

SMAX

stops flashing.

4.

Press the

or

buttons to enter the

measured airflow.

5.

Press the

Set

Point

button to save the measured

airflow. The display advances to

SMIN

.

SMAX

OO

The airflow balancing procedure (continued)

Section 5: Balancing airflow

SimplyVAV

46

Revision E