Procedure
Steps
STE display
5
Advance or exit
1.
Press the or buttons to select one of the
following:
SEC
to balance the secondary VAV for dual
duct systems. Choosing
SEC
advances to
the
SMAX
display. This is available only on
dual duct models.
BACK
to choose another commissioning
function
EXIT
to return to the temperature display.
2.
Press the
Set
Point
button to select the next function.
PRI
SEC
6
Measure and enter the
actual maximum
secondary airflow
The display begins flashing
SMAX
and also
displays the actual airflow at the bottom.
Note:
The airflow displayed by the STE-8000
in this step is the actual, uncorrected airflow.
1.
Wait for the maximum airflow value to
stabilize.
2.
With a flow hood, measure the actual airflow.
3.
Press the
Set
Point
button to advance to the entry
display.
SMAX
stops flashing.
4.
Press the
or
buttons to enter the
measured airflow.
5.
Press the
Set
Point
button to save the measured
airflow. The display advances to
SMIN
.
SMAX
OO
The airflow balancing procedure (continued)
Section 5: Balancing airflow
SimplyVAV
46
Revision E