KMC Controls SAE-1162 User Manual
Installation guide, Carbon monoxide (co) detectors, Mounting 1

SAE-1111/1112/1162 Carbon Monoxide (CO) Detectors
1
Installation Guide
Installation Guide
Carbon Monoxide (CO) Detectors
SAE-1111/1112/1162
Calibration 8
Models 9
Accessories 9
Maintenance 9
Important Notices 9
More Information 9
SAE-1111/1112 Space Mount
Install the unit at least five feet above the finished
floor of the area to be controlled. Do not install
near doors, windows, supply air diffusers of other
known air disturbances. Avoid areas prone to vibra-
tion or rapid temperature change.
1. On the mounting surface, mark and drill the four
mounting holes (for screws) and remove any
debris from all holes.
2. Attach the unit to the surface by threading four
screws through the four mounting holes.
3. Remove the two cover screws (if installed),
release the latch, and swing open the cover.
4. Insert wiring through a knockout.
5. After wiring, configuring, and testing the
unit (see later sections), close the cover and
(optionally) secure it with two (supplied) self-
tapping screws.
SAE-1162 Duct Mount
Choose a mounting location in a straight section of
a return air duct. Mount at least 5 feet (or 7.5 duct
diameters) from corners and other items that may
cause disturbances in the air flow. Avoid areas prone
to vibration or rapid temperature change.
1. Cut a 1-1/8 or 1-1/4 inch hole in the duct for the
air sampling probe.
2. Insert the probe through the hole, align the unit
so that the duct air flow is parallel with the side
vent holes in the probe (air flows directly into
the probe holes), and mark the four enclosure
mounting holes.
3. Drill the four mounting holes (for screws) and
remove any debris from all holes.
4 . Insert the sampling probe into the duct.
5. Attach the unit to the ductwork by threading four
screws through the four holes on the outside of
the enclosure.
6. Remove the two cover screws (if installed),
release the latch, and swing open the cover.
7. Insert wiring through a knockout. After wiring a
duct sensor, fill the knockout hole with plumber’s
Mounting
145 mm
5.7"
101 mm
4"
114 mm
4.5"
89 mm
3.5"
ALARM
64 mm
2.5"
240 mm
9.5"
26 mm
1"
177 mm
7.0"
145 mm
5.7"
101 mm
4"
114 mm
4.5"
89 mm
3.5"
ALARM
64 mm
2.5"
SAE-1111/1112
SAE-1162
putty, caulk, or other sealant to prevent air
infiltration from the conduit.
8. After wiring, configuring, and testing the
unit (see later sections), close the cover and
(optionally) secure it with two tapping screws.