SAE-1111/1112/1162 Carbon Monoxide (CO) Detectors

1

Installation Guide

Installation Guide

Carbon Monoxide (CO) Detectors

SAE-1111/1112/1162

Mounting 1

SAE-1111/1112 Space Mount 1

SAE-1162 Duct Mount 1

Wiring 2
Operation 3

Warm-Up Mode

3

Normal Mode

3

Alarm Mode

3

Configuration 4

Test Mode

4

Fault Mode

4

ReCal (Recalibration) Mode

4

Calibration 8
Models 9
Accessories 9
Maintenance 9
Important Notices 9
More Information 9

SAE-1111/1112 Space Mount

Install the unit at least five feet above the finished

floor of the area to be controlled. Do not install

near doors, windows, supply air diffusers of other

known air disturbances. Avoid areas prone to vibra-

tion or rapid temperature change.
1. On the mounting surface, mark and drill the four

mounting holes (for screws) and remove any

debris from all holes.

2. Attach the unit to the surface by threading four

screws through the four mounting holes.

3. Remove the two cover screws (if installed),

release the latch, and swing open the cover.

4. Insert wiring through a knockout.
5. After wiring, configuring, and testing the

unit (see later sections), close the cover and

(optionally) secure it with two (supplied) self-

tapping screws.

SAE-1162 Duct Mount

Choose a mounting location in a straight section of

a return air duct. Mount at least 5 feet (or 7.5 duct

diameters) from corners and other items that may

cause disturbances in the air flow. Avoid areas prone

to vibration or rapid temperature change.
1. Cut a 1-1/8 or 1-1/4 inch hole in the duct for the

air sampling probe.

2. Insert the probe through the hole, align the unit

so that the duct air flow is parallel with the side

vent holes in the probe (air flows directly into

the probe holes), and mark the four enclosure

mounting holes.

3. Drill the four mounting holes (for screws) and

remove any debris from all holes.

4 . Insert the sampling probe into the duct.
5. Attach the unit to the ductwork by threading four

screws through the four holes on the outside of

the enclosure.

6. Remove the two cover screws (if installed),

release the latch, and swing open the cover.

7. Insert wiring through a knockout. After wiring a

duct sensor, fill the knockout hole with plumber’s

Mounting

145 mm

5.7"

101 mm

4"

114 mm

4.5"

89 mm

3.5"

ALARM

64 mm

2.5"

240 mm

9.5"

26 mm

1"

177 mm

7.0"

145 mm

5.7"

101 mm

4"

114 mm

4.5"

89 mm

3.5"

ALARM

64 mm

2.5"

SAE-1111/1112

SAE-1162

putty, caulk, or other sealant to prevent air

infiltration from the conduit.

8. After wiring, configuring, and testing the

unit (see later sections), close the cover and

(optionally) secure it with two tapping screws.