This installation sheet applies to SimplyVAV digital

wall sensors connected to SimplyVAV

controllers. For additional information on

the SimplyVAV products, browse to the

SimplyVAV web site for videos and other

resources.

Choosing a sensor location

Install the sensor on an inside wall where it can sense

the average room temperature. Avoid locations with

direct sunlight, heat sources, windows, air vents,

and air circulation obstructions such as curtains or

furniture.
For models with motion sensing, see the topic on the

following page, Planning for motion sensing.

Rough-in preparation

Complete rough-in wiring at each sensor location

prior to sensor installation. This includes the following

items.

If required, install an appropriate backplate.

Route an Ethernet connecting cable from the

sensor to the controller location.

Maximum cable length is 75 feet (22.9 meters).

Plenum-rated preassembled cables are

recommended.

Turn clockwise to

remove from base.

Turn counterclockwise

until the screws engage

the case.

Mount the sensors

To install the sensor on a mounting base, do the

following:

1. Turn the Allen screws in the base of the sensor

clockwise until they clear the case. Swing the

sensor away from the mounting base to remove it.

2. Route the Ethernet cable through the mounting

base.

3. Fasten the mounting base directly to a 2 x 4 inch

outlet box or a backplate with the Allen screws

toward the floor.

4. Insert the Ethernet cable coming from the base

into the sensor.

5. Place the top of the sensor over the top of the

mounting base and swing it down over the Allen

screw brackets. Be careful not to pinch any wiring.

6. Turn the Allen screws counterclockwise until they

back out of the mounting base and engage the

case of the sensor.

Mounting

base

Ethernet

connecting cable

Maximum 75 feet

or 22.9 meters

Allen

screws

Operation

The sensor will become operational as soon as it

is connected to an operational controller. See the

following pages to change room setpoints or configure

a SimplyVAV controller with the sensor.

Maintenance

Remove dust as necessary from holes in top and

bottom. Clean the display with soft, damp cloth and

mild soap.