Pmax, Pmin – KMC Controls BAC-8007 Installation Guide User Manual
Page 45

Procedure
Steps
STE display
3
Measure and enter the
actual maximum primary
airflow
The display begins flashing
PMAX
and also
displays the actual airflow at the bottom.
Note:
The airflow will attempt to stabilize on
the highest value for either the cooling or
heating maximum airflow even if only one
mode is operational.
Note:
The airflow displayed by the STE-8000
in this step is the actual, uncorrected airflow.
1.
Wait for the maximum airflow value to
stabilize.
2.
With a flow hood, measure the actual airflow.
3.
Press the
Set
Point
button to advance to the entry
display.
PMAX
stops flashing.
4.
Press the
or
buttons to enter the
measured airflow.
5.
Press the
Set
Point
button to save the measured
airflow. The display changes to
PMIN
.
PMAX
OO
4
Measure and enter the
actual minimum primary
airflow
The display begins flashing
PMIN
and also
displays the actual airflow at the bottom.
Note:
The airflow will attempt to stabilize on
the lowest value for either the cooling or
heating minimum airflow even if only one
mode is operational.
Note:
The airflow displayed by the STE-8000
in this step is the actual, uncorrected airflow.
1.
Wait for the minimum airflow value to
stabilize.
2.
With a flow hood, measure the actual airflow.
3.
Press the
Set
Point
button to advance to the entry
display.
PMIN
stops flashing.
4.
Press the
or
buttons to enter the
measured airflow.
5.
Press the
Set
Point
button to save the measured
airflow. The display advances to
PRI
.
PMIN
OO
The airflow balancing procedure (continued)
SimplyVAV
Section 5: Balancing airflow
Revision E
45