Pmax, Pmin – KMC Controls BAC-8007 Installation Guide User Manual

Page 45

background image

Procedure

Steps

STE display

3

Measure and enter the
actual maximum primary
airflow

The display begins flashing

PMAX

and also

displays the actual airflow at the bottom.

Note:

The airflow will attempt to stabilize on

the highest value for either the cooling or
heating maximum airflow even if only one
mode is operational.

Note:

The airflow displayed by the STE-8000

in this step is the actual, uncorrected airflow.

1.

Wait for the maximum airflow value to
stabilize.

2.

With a flow hood, measure the actual airflow.

3.

Press the

Set

Point

button to advance to the entry

display.

PMAX

stops flashing.

4.

Press the

or

buttons to enter the

measured airflow.

5.

Press the

Set

Point

button to save the measured

airflow. The display changes to

PMIN

.

PMAX

OO

4

Measure and enter the
actual minimum primary
airflow

The display begins flashing

PMIN

and also

displays the actual airflow at the bottom.

Note:

The airflow will attempt to stabilize on

the lowest value for either the cooling or
heating minimum airflow even if only one
mode is operational.

Note:

The airflow displayed by the STE-8000

in this step is the actual, uncorrected airflow.

1.

Wait for the minimum airflow value to
stabilize.

2.

With a flow hood, measure the actual airflow.

3.

Press the

Set

Point

button to advance to the entry

display.

PMIN

stops flashing.

4.

Press the

or

buttons to enter the

measured airflow.

5.

Press the

Set

Point

button to save the measured

airflow. The display advances to

PRI

.

PMIN

OO

The airflow balancing procedure (continued)

SimplyVAV

Section 5: Balancing airflow

Revision E

45