Pkft, Skft, Reht – KMC Controls BAC-8007 Installation Guide User Manual
Page 32

Procedure
Detailed steps
STE display
3
Set the primary VAV
terminal unit K-factor.
The K-factor is supplied by the manufacturer of
the VAV terminal unit. Typically it is on the label
with the unit airflow information.
1.
Press the
or
buttons to set the primary
K-factor.
2.
Press the
Set
Point
button to save the entry and
advance to the next function.
9O4
PKFT
4
Set the secondary VAV
terminal unit K-factor.
Not used in all models.
The K-factor is supplied by the manufacturer of
the VAV terminal unit. Typically it is on the label
with the unit airflow information.
1.
Press the
or
buttons to set the secondary
K-factor.
2.
Press the
Set
Point
button to save the entry and
advance to the next function.
9O4
SKFT
5
Set the mode of reheat
for the terminal unit.
Not used in all models.
1.
Press the
or
buttons to choose one of the
following reheat options.
None
—Reheat is not enabled.
Staged
—Enables staged reheat.
Modulating
—The analog reheat output varies
from 0-10 volts DC.
Floating
—The reheat outputs control a tristate
actuator.
Time proportional
—Controls a thermal wax
valve with a 24-volt triac output.
2.
Press the
Set
Point
button to save the reheat option
and advance to the next function.
NONE
REHT
Procedure to set the box functions (continued)
Section 4: Configuring the controllers
SimplyVAV
32
Revision E