Restore Application
Choose the RSTR function to reset the SimplyVAV controller to the original
configuration and settings. Use it also to change the units of measure to
display on a SimplyVAV sensor. There are two versions of the application
program in the controller.
The Metric version displays temperature in Celsius and uses metric
values for units of measure.
The English version displays temperature in Fahrenheit and uses English
values for units of measure.
Access to the Restore Application function requires entering Password 2
which is described in the topic
Getting started with configuration
.
Tip:
Once the following procedure is started, all steps must be completed in
order.
Caution
Choosing RSTR deletes all previously configured values
including balancing values and passwords. Only the
BACnet communications settings will remain unchanged.
Procedure
Detailed steps
STE display
1
Starting display
1.
Start at the temperature display.
2.
Press the
and
buttons together.
l
If Password 2 is not required, the display
changes to
CNFG
.
l
If required, enter Password 2. The display
changes to
CNFG
when Password 2 is
correct.
3
237
////
Procedure to restore application
Section 4: Configuring the controllers
SimplyVAV
40
Revision E