Restore Application

Choose the RSTR function to reset the SimplyVAV controller to the original
configuration and settings. Use it also to change the units of measure to
display on a SimplyVAV sensor. There are two versions of the application
program in the controller.

The Metric version displays temperature in Celsius and uses metric
values for units of measure.

The English version displays temperature in Fahrenheit and uses English
values for units of measure.

Access to the Restore Application function requires entering Password 2
which is described in the topic

Getting started with configuration

on page 26

.

Tip:

Once the following procedure is started, all steps must be completed in
order.

Caution

Choosing RSTR deletes all previously configured values
including balancing values and passwords. Only the
BACnet communications settings will remain unchanged.

Procedure

Detailed steps

STE display

1

Starting display

1.

Start at the temperature display.

2.

Press the

and

buttons together.

l

If Password 2 is not required, the display
changes to

CNFG

.

l

If required, enter Password 2. The display
changes to

CNFG

when Password 2 is

correct.

3

237

////

Procedure to restore application

Section 4: Configuring the controllers

SimplyVAV

40

Revision E