reheat, the reheat output is modulated over the span of the Reheat loop. If the
Reheat loop is less than 10%, the reheat output remains at zero. The reheat is
set to zero if the Cooling loop is active.

See the topic

Modulating reheat

on page 52

for an application drawing.

Illustration 7–4 Modulating reheat operation

Room temp increase

HTG SP

-2F

HTG SPAN

lo

o

p

%

0

100

10

HTG %

R

e

h

e

a

t

Staged reheat

If the controller is configured for staged reheat, it can control up to three
stages of reheat through binary triac outputs. The reheat outputs are
commanded

On

when the Reheat loop rises above the

On

threshold and

Off

when the loop drops below the

Off

threshold. Thresholds are described in the

following chart,

Staged reheat thresholds

on page 67

.

See the topic

Staged reheat

on page 51

for an application drawing.

Heating stages

Output state

On threshold

Off threshold

Stage 1

35%

15%

Stage 2

65%

45%

Stage 3

95%

75%

Table 7–1

Staged reheat thresholds

Time proportioned reheat

For controllers configured for time proportional reheat, the duty cycle of a
binary triac output varies over a 10 second period. For example, if the Reheat

SimplyVAV

Section 7: Sequences of operation

Revision E