Advc – KMC Controls BAC-8007 Installation Guide User Manual
Page 39

Procedure
Steps
STE display
8
Set the automatic
occupancy mode.
Requires a discharge air
temperature sensor.
1.
Press the
or
buttons to enable or disable
discharge air temperature limiting.
2.
Press the
Set
Point
button to save the setpoint and
advance to the next function.
Enable
The controller will automatically
changed to the unoccupied state when it
detects the loss of primary air supply.
Disable
The controller will remain in the
occupied mode regardless of the primary
air supply.
$)3!",%
!5-$
9
Set the temperature
sensor calibration
constant.
1.
Press the
or
buttons to set the calibration
constant. The setpoint will change in 0.1
minute increments.
l
For a low input reading enter a positive
correction value.
l
For a high input reading enter a negative
correction value.
2.
Press the
Set
Point
button to save the setpoint and
advance to the next function.
OO
CALIB
10
Select a new
configuration function or
exit.
1.
Press the
or
buttons to select one of the
following:
STPT
,
FLOW
,
BOX
, or
RSTR
options
BACK
to choose .another configuration
function
EXIT
to return to the temperature display.
2.
Press the
Set
Point
button to select the next function.
ADVC
Procedure to set the advanced options (continued)
SimplyVAV
Section 4: Configuring the controllers
Revision E
39