Advanced options
The advanced options set up passwords and special features in the controller.
Establish or change Password 1 and Password 2
Set timers for standby and override (optional)
Enable automatic occupancy (optional)
Enable discharge air temperature control (optional)
Calibrate the sensor
Setting the advance options requires entering Password 2 which is described
in the topic
Getting started with configuration
.
Tip:
Once the following procedure is started, all steps must be completed in
order.
Procedure
Steps
STE display
1
Starting display
1.
Start at the temperature display.
2.
Press the
and
buttons together.
l
If Password 2 is not required, the display
changes to
CNFG
.
l
If required, enter Password 2. The display
changes to
CNFG
when Password 2 is
correct.
3
237
////
2
Select the advanced
display.
1.
From the
CNFG
display, press the
Set
Point
button to
show the
STPT
display.
2.
Press the
or
buttons to change the
display to
ADVC
.
3.
Press the
Set
Point
button to select
ADVC
.
CNFG
STPT
ADVC
Table 4–1
Procedure to set the advanced options
SimplyVAV
Section 4: Configuring the controllers
Revision E
37