Connecting an
airflow sensor

An airflow sensor is incorporated as one of the inputs to the controller.
Remove the plugs and connect the tubing from the pitot assembly to the
airflow sensor inputs next to the drive hub.

Illustration 2–3 Airflow sensor inputs

ON CTS

1 2

COMM
READY

24VAC

T

-S
T

A

T

/

SEN

SO

R

-A

+B

S

EO

L

BACnet MS/TP

Total airflow (high) Static airflow (low)

Typically, airflow sensors are supplied by the manufacturer as part of the
VAV terminal unit. If a sensor is needed, choose a sensor listed in the topic

Accessories and replacement parts

on page 11

.

Connecting inputs
and outputs

SimplyVAV series controllers have preconfigured inputs and outputs to
support only the supplied programs and applications.

For input and output connection information, see the topic

Application

drawings

on page 49

.

To connect room temperature sensors, see the topic

Connecting room

temperature sensors

on page 19

To connect a DAT sensor, see the topic

Connecting a DAT sensor

on page

20

.

For the BACnet object descriptions of the inputs and outputs, see the
topic

BACnet objects

on page 77

.