Set the airflow setpoints – KMC Controls BAC-8007 Installation Guide User Manual
Page 34

Set the airflow
setpoints
The airflow setpoints set the airflow limits for the VAV terminal unit.
Airflow heating and cooling minimum and maximum limits
Auxiliary flow setpoint (optional)
Minimum and maximum fan speeds (optional)
Setting the airflow setpoints requires entering Password 2 which is described
in the topic
Getting started with configuration
Note:
If the VAV unit is a heat only or cooling only unit, the airflow setpoints for
the unused mode must be set within the range of the mode in use. Failure to
set the unused setpoints correctly will result in unpredictable or erroneous
air balancing settings.
Tip:
Once the following procedure is started, all steps must be completed in
order.
Procedure
Detailed steps
STE display
1
Starting display
1.
Start at the temperature display.
2.
Press the
and
buttons together.
l
If Password 2 is not required, the display
changes to
CNFG
.
l
If required, enter Password 2. The display
changes to
CNFG
when Password 2 is
correct.
3
237
////
Procedure to set the airflow setpoints
Section 4: Configuring the controllers
SimplyVAV
34
Revision E